 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10
  
 PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR
 FLASH PROTECTION, HIGH-LEG MARKING, PANEL BOARDS AND
 THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16,
 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC ENERGY CONSERVATION T505.3
  
 INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED
 TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE MDP. NEC
 314.28
  
 NOTE:
 SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE SYSTEMS,
 AUDIO , SECURITY, FIRE ALARM, DATA, POS, ETC.
  