Plan Review Notes For Permit 13020210 |
Permit Number |
13020210 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-03-07 13:59:07 | 13020210 | | 701 S. ROSEMARY AVENUE #316 | | H&M BUILDING RENOVATION | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | ELECTRICAL SERVICE AND SWITCH GEAR. NEC 110.9, 110.10 | | | | PROVIDE A SAFETY LABELING SCHEDULE ON THE PLAN FOR | | FLASH PROTECTION, HIGH-LEG MARKING, PANEL BOARDS AND | | THE MAIN DISCONNECTING MEANS. NEC 110.22, 110.16, | | 110.22 | | | | PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLANS SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC ENERGY CONSERVATION T505.3 | | | | INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED | | TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE MDP. NEC | | 314.28 | | | | NOTE: | | SEPARATE PERMITS ARE REQUIRED FOR LOW VOLTAGE SYSTEMS, | | AUDIO , SECURITY, FIRE ALARM, DATA, POS, ETC. | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|