Plan Review Notes For Permit 13020122 |
Permit Number |
13020122 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-07 16:12:35 | RESIDENTIAL (R3) FLAT ROOF RE-ROOF BUILDING REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- FLAT ROOF PRODUCT APPROVAL FL1654-R11 SUBMITTED: | | | | A) DESIGN PRESSURES FOR SELECTED ASSEMBLY (W-29) ARE | | TOO LOW. THEY DON'T MEET THE DESIGN PRESSURES REQUIRED | | BY SEC. R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL FOR THE | | PERIMETER AND CORNER AREAS. NEED TO PROVIDE SIGNED AND | | SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #8 OF | | FLORIDA PRODUCT APPROVAL SUBMITTED. | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING | | TO SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED IN | | EXPOSURE "D". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|