Plan Review Notes
Plan Review Notes For Permit 13020033
Permit Number 13020033
Review Stop B
Sequence Number 1
Notes
Date Text
2013-02-04 16:58:072010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY WHICH ONE OF THE FASTENING OPTIONS AND
 DESIGN PRESSURES LISTED ON PAGE 27 OF THE NOA FOR THE
 GAF MODIFIED ROOF SYSTEM WILL BE USED. FBCR 905.11.3
  
 2) SUBMIT TWO COPIES OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY
 LIMITATION NUMBER 7 ON PAGE 31 OF THE NOA. FBCR
 905.11.3 AND CITY AMENDMENTS 107.2.1.4
  
 3) PER FBC EXISTING BUILDING SECTION 611.1.1, NOT MORE
 THAN 25 PER CENT OF THE TOTAL ROOF AREA OR ROOF SECTION
 OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE. PROVIDE TWO
 COPIES OF A DIMENSIONED DIAGRAM OF THE ROOF INDICATING
 THE AREA OF THE PROPOSED REPAIRS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]