Plan Review Notes For Permit 13010963 |
Permit Number |
13010963 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-01 10:41:45 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. FOR THE FLAT DECK, TWO DIFFERENT ASSEMBLIES ARE | | INDICATED. NEITHER MEETS THE PRESSURES FOR PERIMETER | | AND CORNER ZONES; ONE HAS A LIMITATION OF -45PSF, THE | | OTHER HAS A LIMITATION OF -52.5. CLARIFY WHICH ASSEMBLY | | IS PROPOSED AND PROVIDE A SPECIFICATIN FOR ENHANCED | | FASTENING. FBC R 301. | | | | 2. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE | | REQUIREMENTS CAN BE DETERMINED FBC R 301. | | | | 3. FOR THE TILE, INDICATE WHICH METHOD OF ATTACHMENT IS | | PROPOSED FBC R 301. |
|