Plan Review Notes
Plan Review Notes For Permit 13010963
Permit Number 13010963
Review Stop B
Sequence Number 1
Notes
Date Text
2013-02-01 10:41:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FOR THE FLAT DECK, TWO DIFFERENT ASSEMBLIES ARE
 INDICATED. NEITHER MEETS THE PRESSURES FOR PERIMETER
 AND CORNER ZONES; ONE HAS A LIMITATION OF -45PSF, THE
 OTHER HAS A LIMITATION OF -52.5. CLARIFY WHICH ASSEMBLY
 IS PROPOSED AND PROVIDE A SPECIFICATIN FOR ENHANCED
 FASTENING. FBC R 301.
  
 2. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED FBC R 301.
  
 3. FOR THE TILE, INDICATE WHICH METHOD OF ATTACHMENT IS
 PROPOSED FBC R 301.