2013-02-01 09:47:56****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FOR THE FLAT DECK, TWO DIFFERENT ASSEMBLIES ARE
 INDICATED. NEITHER MEETS THE PRESSURES FOR PERIMETER
 AND CORNER ZONES; ONE HAS A LIMITATION OF -45PSF, THE
 OTHER HAS A LIMITATION OF -52.5. CLARIFY WHICH ASSEMBLY
 IS PROPOSED AND PROVIDE A SPECIFICATIN FOR ENHANCED
 FASTENING. FBC R 301.
  
 2. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED FBC R 301.
  
 3. FOR THE TILE, INDICATE WHICH METHOD OF ATTACHMENT IS
 PROPOSED FBC R 301.
  
 4. WPB ADMIN CODE 94-546(B), WHEN LIFETIME CUMULATIVE
 IMPROVEMENTS TO A STRUCTURE EXCEED 50% OF THE STRUCTURE
 VALUE, THE STRUCTURE IS TO BE BROUGHT INTO COMPLIANCE
 WITH FEMA REQUIREMENTS. PLEASE PROVIDE A COPY OF A
 CERTIFIED APPRAISAL FOR THIS PROPERTY. PLEASE CONTACT
 ME IF THE APPRAISAL IS NOT AVAILABLE.
  
  