2013-02-23 11:18:49477 SOUTH ROSEMARY AVENUE - SUITE #169
 PERMIT #13010955
 MASTER #12100295
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ORIGINAL COMMENT:THE FIRE PROTECTION ENGINEER OF RECORD
 (DINO PAPPAS) ON THE CONSTRUCTION DOCUMENTS (SHEET FP1)
 INDICATES THE SYSTEM SHALL BE DESIGNED FOR ORDINARY
 HAZARD GROUP II. THE SPRINKLER SHOP DRAWINGS INDICATE
 THE SYSTEM IS DESIGNED FOR LIGHT HAZARD.
 RESPONSE COMMENT: THE LETTER FROM MR. PAPPAS (P.E.) IS
 NOT SEALED AND THEREFORE CANNOT BE ACCEPTED AS CHANGING
 THE DESIGN CRITERIA PER FLORIDA STATUTES. ADDITIONALLY,
 FIRE PROTECTION NOTE #3 ON SHEET FP1 CLEARLY STATES,
 "THE SYSTEM SHALL BE DESIGNED FOR ORDINARY HAZARD GROUP
 II." A REVISION TO (SHEET FP1) OF THE ENGINEERING
 CONSTRUCTION DOCUMENTS NEEDS TO BE SUBMITTED
 (SIGNED/SEALED) BY THE ENGINEER.
  
 REPEAT COMMENT: NO WATER SUPPLY INFORMATION INDICATED
 ON THE PLANS.
  
 REPEAT COMMENT: NO HORIZONTAL SIDEWALL SPRINKLER
 INFORMATION PROVIDED IN THE SPRINKLER SCHEDULE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730