Plan Review Notes For Permit 13010955 |
Permit Number |
13010955 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-05 10:29:16 | 477 SOUTH ROSEMARY AVENUE - SUITE #169 | | PERMIT #13010955 | | MASTER #12100295 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE FIRE PROTECTION ENGINEER OF RECORD (DINO PAPPAS) ON | | THE CONSTRUCTION DOCUMENTS (SHEET FP1) INDICATES THE | | SYSTEM SHALL BE DESIGNED FOR ORDINARY HAZARD GROUP II. | | THE SPRINKLER SHOP DRAWINGS INDICATE THE SYSTEM IS | | DESIGNED FOR LIGHT HAZARD. | | | | FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING) | | INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR | | UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM | | SPRINKLER DISTANCE BELOW THE STRUCTURE/ROOF DECK (IF | | OBSTRUCTED CONSTRUCTION). | | | | NO WATER SUPPLY INFORMATION OR HYDRAULIC CALCULATIONS | | SUBMITTED. | | | | NO HORIZONTAL SIDEWALL SPRINKLER INFORMATION PROVIDED | | IN THE SPRINKLER SCHEDULE. | | | | INDICATE THE REASON FOR THE EXPOSED PIPE/DROP NIPPLE IN | | HEAD DETAIL #3. | | | | THE SPRINKLERS IN THE CEILING CLOUDS (8'-6" AFF) ALONG | | COLUMN LINE 8 ARE LOCATED MORE THAN 7'-6" FROM ONE | | EDGE. | | | | WESLEY JOLIN | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 | | |
|