2013-06-13 14:05:07 | BUILDING PLAN REVIEW |
| PERMIT: 13010796 |
| ADD: 3401 PARKER AVE |
| CONT: HEDRICK BROTHERS |
| TEL: (561)689-8880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| *******INFORMATIONAL:***** WHEN RESUBMITTING PLANS |
| PLEASE INDICATE THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. PLANS WILL NOT BE ISSUED |
| UNTIL THE NEW SHEETS ARE INSERTED INTO THE PLANS. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1) MISSING DOCUMENTS FOR COMMERCIAL PLAN REVIEW. 2010 W |
| P B ADMINISTRATIVE CODE 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3 |
| 1A) CCOMPLIED. SOILS REPORT. |
| |
| 1B) PROVISO |
| BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| BUILDING ENVELOPE STEEL BUILDING/ CALCULATIONS, MISSING |
| THE STEEL BUILDING ENGINEERING |
| |
| |
| 1C) BUILDING APPROVED WITH EXCEPTION! |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| PRODUCT APPROVALS RULE 9N-3 (31) FLORIDA DEPARTMENT OF |
| COMMUNITY AFFAIRS RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (E) SHUTTERS |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 2. ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| FOLLOWING: |
| 2A)SITE REQUIREMENTS |
| 2B) ACCESSIBLE ROUTE |
| |
| 3) ENERGY CODE 103.1 CONSTRUCTION DOCUMENTS. |
| |
| 4) COMPLIED, RESPONCE INDICATES ON SHEET ESSP1 & ESSP 2 |
| BOTH INDICATE TO BE OPEN TENNIS PAVILIONS OF 836 SQ FT |
| PER BUILDING AS FUTURE BUILDINGS NOT PART OF THIS |
| CONTRACT THEY WILL BE STRUCK.. |
| |
| |
| 5) PROVISO: SHEET ESSP 1 & 3 INDICATE A PROPOSED 6 FT |
| TALL CONCRETE PRECAST SCREEN WALL. A SEPERATE PERMIT |
| APPLICATION, WILL BE REQUIRED FOR INSPECTIONS AND |
| RECORD RETENTION. 2010 WPB ADMINISTRATIVE CODE 105.1. |
| |
| 6) COMPLIED. |
| |
| 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |
| |
| |
| |
| |