Plan Review Notes For Permit 13010726 |
Permit Number |
13010726 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-06 12:01:51 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. SEE DETAIL M REGARDING MINIMUM EDGE DISTANCE, SHEET | | 7 AND REVISE INSTALLATION SCHEDULE. | | | | 2. THIS PARCEL IS LOCATED IN EXPOSURE C, SEE FBC | | 1609.4. | | | | 3. PLEASE CLARIFY, CONNECTION TYPE IS STATED AS "MS" ON | | INSTALLATION SCHEUDLE, STEEL SUBSTRATE. M IS FOR | | CONCRETE, S IS FOR WOOD. ENGINEERING REQUIRED IF YOUR | | CONNECTION METHOD IS NOT ADDRESSED IN THE PRODUCT | | APPROVAL. | | | | |
|