Plan Review Notes For Permit 13010720 |
Permit Number |
13010720 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2013-07-15 14:21:31 | PASS PROVISO | | REVISION REQUIRED | | 1) MISSING FIRE DAMPER ON PAGE M3.0 | | FCU-11-04 . PER SECTION 607.5.1 FIRE WALLS | | 2010 FBC (M) | | 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | CURB TO ROOF TIE DOWN INCLUDING BOLT SIZE | | AND BOLT PATTERN. PROVIDE BOLT SIZE FOR THE RTU. TO | | CURB TIE DOWN | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|