2013-04-25 16:44:36 | BUILDING PLAN REVIEW |
| PERMIT: 13010720 |
| ADD: 700 S ROSEMARY # 104 |
| CONT: TBD |
| CONTACT: JORGE BENAVIDES |
| TEL: (561)632-1900 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| APRIL 25/ 2013 |
| ACTION: DENIED |
| |
| 1) COMPLIED. |
| |
| 2) COMPLIED. |
| |
| 3) SHEET A-0.0 & A-2.2 THE OCCUPANT LOAD COUNT IS TAKEN |
| AS 50 SQ FT PER PERSON IS WITH EQUIPMENT, BOTH FIRE AND |
| THE BUIULDING OFFICIAL CONCUR THAT THE MATS COULD BE |
| REMOVED AND A HIGH OCCUPANT LOAD BE ACHIEVED SUCH AS |
| LINE DANCING OR SOME SIMILAR ACTIVITY. FOR THE PURPOSE |
| OF THIS REVIEW THE 15 SQ FT WILL BE USED FOR THE |
| OCCUPANT LOAD COUNT. PLEASE CORRECT THE OCCUPANT LOAD |
| AND REQUIRED EGRESS WIDTHS FOR THE SECOND FLOOR. |
| |
| 4)2010 EXST BLDG CODE 912.4.1 MEANS OF EGRESS FOR |
| CHANGE TO HIGHER HAZARD CATEGORY. |
| WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| 912.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 4A) THE MONUMENTAL STAIR IS NOW BEING ASKED TO BE A |
| PART OF A MEANS OF EGRESS. THE TENANT SPACE IS NOW A |
| (A-3 OCCUPANCY) WHERE IT WAS NOT UNDER THE MERCANTILE |
| OCCUPANCY. THE EXCEPTION FOR MONUMENTAL STAIRS IS FOUND |
| UNDER 708.2 EXCEPTION # 7, THE MONUMENTAL STAIR NOT |
| REQUIRED TO BE PART OF THE MEANS OF EGRESS BECAUSE |
| THERE WERE 2 VERTICAL EXITS TO THE 2ND FLOOR. |
| |
| THE 2010 FBC-B SECTION 1028.2 (ASSEMBLY REQUIRES 50 % |
| OF THE TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN |
| ENTRANCE/ EXIT. ONE QUESTION IS HOW DO YOU GET THE |
| OCCUPANTS TO THE SECOND FLOOR? THE ELEVATOR AND THE |
| MONUMENTAL STAIR ARE THE ONLY WAY TO THE 2ND FLOOR. |
| |
| 1028.3 ASSEMBLY OTHER EXITS. EACH LEVEL OF AN ASSEMBLY |
| OCCUPANCY SHALL HAVE ACCESS TO A MAIN EXIT AND SHALL BE |
| PROVIDED WITH ADDITIONAL EXITS OF SUFFICIENT WIDTH TO |
| ACCOMMODATE ONE-HALF OF THE TOTAL OCCUPANT LOAD SERVED |
| BY THAT LEVEL. SUCH ADDITIONAL EXITS SHALL BE LOCATED |
| AS FAR FROM THE MAIN ENTRANCE/EXIT AS PRACTICABLE. SUCH |
| EXITS SHALL BE ACCESSIBLE FROM A CROSS AISLE OR A SIDE |
| AISLE. PLEASE PROVIDE CODE COMPLIANCE. |
| |
| ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT LOAD |
| ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY 2010 |
| FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON THE |
| 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL ALSO BE |
| REQUIRED. FBC-B 708.2 EXCEPTION 7.2 STATES THAT IT "IS |
| NOT PART OF A MEANS OF EGRESS SYSTEM. |
| |
| THE SECOND AREA TO CONSIDER IS IN SECTION FBC-B 1028.2 |
| THE 50% OF THE TOTAL OCCUPANTS TO EXIT THROUGH THE MAIN |
| ENTRANCE/ EXIT. HOW WOULD YOU GET THE 50 % OCCUPANT |
| LOAD BACK THROUGH THE MAIN ENTRANCE IF YOU ARE |
| CONSIDERING THE BACK ENTRANCE AS ONE OF TWO MAIN |
| ENTRANCES. THE SECOND STORY NORTH EXIT TAKES YOU INTO |
| AN EXIT PASSAGE WAY THEN YOU TAKE A VERTICAL EXIT AND |
| OUT THE EXIT DOORWAY OR THE EXIT DISCHARGE, IT DOES NOT |
| TAKE YOU BACK TO THE MAIN ENTRANCE EXIT. |
| |
| PLEASE REVIEW SECTION FBC-B 1027.1 EXCEPTION# 1, IF THE |
| MONUMENTAL STAIR WERE TO BE ENCLOSED, IT DOES NOT NEED |
| TO LEAD TO THE EXTERIOR OF THE BUILDING ONLY BE A 1 |
| HOUR RATED SHAFT WITH OPENING PROTECTIVES 1ST AND 2ND |
| FLOOR, THIS WOULD SOLVE YOUR ISSUES WITH HOW YOU ARE |
| GETTING OCCUPANTS TO THE 2ND FLOOR AND HOW 50 % OF THE |
| OCCUPANTS ARE TRAVELING BACK TO THE MAIN ENTRANCE/ |
| EXIT, FOR EITHER ENTRANCE. |
| |
| 4B) ANOTHER ISSUE THAT IS BORDER LINE IS THE OCCUPANT |
| LOAD ON THE SECOND FLOOR AND A THIRD REQUIRED STAIRWAY |
| 2010 FBC-B TABLE 1021.1 IF 501 OCCUPANTS ARE LOCATED ON |
| THE 2ND FLOOR THEN A THIRD REQUIRED EXIT STAIR WILL |
| ALSO BE REQUIRED. PLEASE REVIEW THE OCCUPANT LOAD FOR |
| THE AEROBICS ROOM THE OCCUPANT LOADS ARE TO BE |
| CONSIDERED AT 15 NET, FBC-B 1004.1.1. |
| |
| 5) THE PLANS DO PROVIDE A SECTION THROUGH THE |
| MONUMENTAL STAIRWAY,INDICATING THE USE OF A DRAFT |
| CURTAIN BUT FAIL TO INDICATE THE USE OF THE FIRE |
| SPRINKLER LOCATION. NOT FOUND ON THE ARCHITECTURAL NOR |
| THE LEVEL 1 FIRE SPRINKLER PLAN. 2010 FBC-B 708.2 |
| EXCEPTION 2.1. WHERE THE AREA OF THE FLOOR OPENING |
| BETWEEN STORIES DOES NOT EXCEED TWICE THE HORIZONTAL |
| PROJECTED AREA OF THE ESCALATOR OR STAIRWAY AND THE |
| OPENING IS PROTECTED BY A DRAFT CURTAIN AND CLOSELY |
| SPACED SPRINKLERS IN ACCORDANCE WITH NFPA 13. IN OTHER |
| THAN GROUPS B AND M, THIS APPLICATION IS LIMITED TO |
| OPENINGS THAT DO NOT CONNECT MORE THAN FOUR STORIES. |
| PLEASE NOTE THIS EXCEPTION IS ONLY FOR BUSINESS & |
| MERCANTILE, NOT FOR AN ASSEMBLY USE, PLEASE PROVIDE HOW |
| THIS CODE VIOLATION WILL BE COMPLIED. |
| |
| 6) THE LIFE SAFETY PLANS HAVE SERIOUS PROBLEMS SINCE |
| THE MONUMETAL STAIRS CAN NOT BE USED FOR EXITING AND |
| SINCE THE 2ND FLOOR OCCUPANT LOAD IS AT 500 OCCUPANTS, |
| NEITHER THE STAIRS NOR THE DOORS AT THE BACK OF THE |
| BUILDING WILL HANDLE THESE OCCUPANT LOADS. THE DESIGNER |
| IS TAKING A 42 INCH DOOR AND STATING 200 OCCUPANTS CAN |
| EXIT THIS OPENING, WHEREAS THE TWO VERTICAL EXITS BACK |
| OF 2ND FLOOR WILL ONLY HANDLE 400 OCCUPANTS. PLEASE |
| PROVIDE A LIFE SAFETY PLAN SHOWING THE EGRESS BACK OF |
| HOUSE FOR THIS TENANT AND THE ADJACENT TENANTS AND |
| PROVIDING A EGRESS PLAN TO THE PUBLIC WAY. PLEASE NOTE |
| THE EGRESS PLAN ALSO HANDLES AN ACCESSIBLE RAMP, STAIRS |
| OUTSIDE OF THE BUILDING, IT ALSO HAS TO TAKE INTO |
| ACCOUNT THE ASSEMBLY OCCUPANCIES ON EITHER SIDE OF THIS |
| NEWLY FORMED A3 OCCUPANCY. |
| |
| THE SAME REQUEST FOR A LIFE SAFETY PLAN FOR THE |
| LANDLORD PERMIT FOR THIS SPACE HAS BEEN REQUESTED, THIS |
| PERMIT WILL NOT BE ISSUED NOR THE LANDLORD TENANT |
| IMPROVEMENT PERMIT UNTIL THIS ISSUE IS CLEARED UP. THE |
| BACK OF HOUSE CORRIDORS ARE 1 HOUR EXIT PASSAGEWAYS, |
| THAT HAVE TO BE TREATED AS SUCH AND THE EXITING HAS TO |
| WORK FOR THE SHARED EXIT PASSAGE WAY. |
| |
| 7-9) COMPLIED. |
| 10) STRUCTURAL WORK COMMENT # 10 TO BE COMPLETED UNDER |
| THE LANDLORD PERMIT# 13030406. |
| |
| 10A) IS THE EXTERIOR STAIR WORK FOUND ON S-1 AND |
| EXTERIOR CANOPY WORK FOUND ON S-2 STILL PART OF THIS |
| PERMIT OR PART OF THE LANDLORD PERMIT. |
| |
| 11) PLANS ARE REQUIRED TO HAVE CITY PLACE APPROVAL WITH |
| THEIR STAMP. |
| |
| 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |