Plan Review Notes
Plan Review Notes For Permit 13010720
Permit Number 13010720
Review Stop M
Sequence Number 1
Notes
Date Text
2013-02-07 14:44:55MECHANICAL PLANS DENIED
 1) PROVIDE DUCT SIZE ON ALL AIR CONDITIONING
 AND EXHAUST DUCT.
 PER SECTION 107 FBC
 2) ELECTRICAL ROOM IS NOT ON MECHANICAL PLANS.
 FAN COIL SCHEDULE SHOWS AN FCU-UL-01
 UNSEALED IN THE ROOM.PER SECTION 107 FBC
 3) ROOF CURB DETAIL # 6 DOES NOT SHOW THE
 SIZE OR TYPE SCREWS FOR ANCHORING TO ROOF
 PER SECTION 301.12 WIND RESISTANCE FBC (M)
 4) MISSING FIRE DAMPERS ON UNIT FCU-LL-03
 PER SECTION 607.5.1 FIRE WALLS FBC (M) 2010
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]