Plan Review Notes For Permit 13010720 |
Permit Number |
13010720 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-02-07 14:44:55 | MECHANICAL PLANS DENIED | | 1) PROVIDE DUCT SIZE ON ALL AIR CONDITIONING | | AND EXHAUST DUCT. | | PER SECTION 107 FBC | | 2) ELECTRICAL ROOM IS NOT ON MECHANICAL PLANS. | | FAN COIL SCHEDULE SHOWS AN FCU-UL-01 | | UNSEALED IN THE ROOM.PER SECTION 107 FBC | | 3) ROOF CURB DETAIL # 6 DOES NOT SHOW THE | | SIZE OR TYPE SCREWS FOR ANCHORING TO ROOF | | PER SECTION 301.12 WIND RESISTANCE FBC (M) | | 4) MISSING FIRE DAMPERS ON UNIT FCU-LL-03 | | PER SECTION 607.5.1 FIRE WALLS FBC (M) 2010 | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|