2013-01-28 09:08:152010 FBC
  
 DENIED BY PLUMBING
  
 1) THE MANUFACTURER'S SPECIFICATIONS FOR THE 1 HP
 HAYWARD 2 SPEED POOL PUMP MODEL # SP2607X102S HAS A
 FLOW RATE OF 85 GPM WITH A 20' TDH. THE PLANS
 INCORRECTLY SPECIFY 75 GPM AT 19.3 TDH AND 2" SUCTION
 PIPING. THE FLOW WILL EXCEED THE ALLOWABLE 8 FT PER
 SECOND VELOCITY IF 2" SUCTION PIPE IS USED WITH A FLOW
 RATE OF 85 GPM. PLEASE CORRECT. FBCR 4101.6.3 AND
 ANSI/APSP-06
  