Plan Review Notes For Permit 13010572 |
Permit Number |
13010572 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-23 14:51:14 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. INDICATE SYSTEM PROPOSED. SEE SHEET 6 OF 16 OF FLAT | | DECK PRODUCT APPROVAL, FBC 1609. THE INFORMATION | | HIGHLIGHTED ON PAGE 3 ARE PRODUCTS (COMPONENTS), A PART | | OF A ROOF ASSEMBLY. | | | | 2. IF THE PROPOSED ASSEMBLY DOES NOT MEET THE MINIMUM | | DESIGN PRESSURE REQUIREMENT OF -102PSF FOR ZONE 3, | | ENGINEERING FOR ENHANCED FASTENING IS REQUIRED, FBC | | 1609. PLEASE NOTE THAT TWO DIFFERENT SYSTEMS MEET THIS | | PRESSURE, SEE SHEET 6. | | | | |
|