2013-01-30 14:35:56MECHANICAL PLANS DENIED
 1) PROVIDE INFORMATION ON THE SIZE FASTENERS USED TO
 ANCHOR
 PIPE STANDS AND UNISTRUT TO ROOF, TO MEET WIND
 RESISTANCE
 PER SECTION 301.12 1210 FBC (M)
 2) PROVIDE A DETAIL ON HOW THE CONDENSER IS ANCHORED TO
 THE ROOF
 PER SECTION 301.12 FBC (M) 2010
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND
 SECTION 606.3 INSTALLATION 2010 FBC (M)
 4) REFER TO SECTION 606.4.1 SUPERVISION .2010 FBC (M)