 400 S. AUSTRALIAN
 INSTALL LIEBERT DX UNITS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SINGLE LINE ELECTRICAL RISER PLAN FOR EQUIPMENT
 CONNECTIONS. PROVIDE SPECIFICATION AND LISTING FOR THE
 INTERLOCKING SYSTEM WHICH PREVENTS BOTH SYSTEMS FROM
 OPERATING TOGETHER. NEC 215.5, 110.3
  
  