2013-04-23 13:42:19 | 610 EVERNIA STREET |
| PERMIT #13010504 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****APPROVED WITH PROVISIONS***** |
| |
| SHEET T101: ADD THE FIRE SPRINKLER ENGINEERING |
| DOCUMENTS TO THEDRAWING SHEET INDEX. |
| |
| SHEET FP1- FP12: CORRECT THE SITE ADDRESS FROM 627 |
| EVERNIA STREET TO 631 EVERNIA STREET. |
| |
| SHEET FP3: PROVIDE SPRINKLER PROTECTION IN EQUIPMENT |
| STORAGE ROOM LOCATED ON POOL DECK. |
| |
| SHEET FP3: THERE APPEAR TO BE SEVERAL SOFFITS |
| OBSTRUCTING SPRINKLER SPRAY IN AND AROUND THE CLUBHOUSE |
| AREA. FOR EXAMPLE SPRINKLERS ARE SHOWN 11'-0' AFF IN |
| THE LIGHT COVE ADJACENT TO STEPPED CEILINGS OF 10'-0" |
| AND 9'-0" AFF. THE SPRINKLER LOCATIONS DO NOT APPEAR TO |
| COMPLY WITH OBSTRUCTION TABLE 8.6.5.1.2 (NFPA 13 - 2007 |
| EDITION). |
| |
| SHEET FP5: WEST STAIR - IT IS DIFFICULT TO DETERMINE IF |
| THE CORRIDOR SPRINKLER WILL PROTECT THE STAIR ENTRY |
| VESTIBULE. |
| |
| SHEET FP12: PROVIDE 2-1/2" FIRE DEPARTMENT STANDPIPE |
| HOSE VALVES WITHOUT THE 1-1/2" REDUCER. |
| |
| FIRE ALARM: PER LOCAL AMENDMENT; DUCT SMOKE DETECTORS |
| SHALL INITIATE A GENERAL ALARM IN LIEU OF A SUPERVISORY |
| ALARM CONDITION. |
| |
| SHEET FA2.1: PROVIDE FIRE ALARM ANNUNCIATOR PANEL IN |
| LOBBY #001 |
| |
| SHEET FA2.1: PROVIDE NOTIFICATION APPLIANCE IN LAUNDRY |
| #015. |
| |
| SHEET FA4.1: PROVIDE NOTIFICATION APPLIANCE IN COMMON |
| LAUNDRY ROOM. TYPICAL EACH FLOOR. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |