Plan Review Notes
Plan Review Notes For Permit 13010504
Permit Number 13010504
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2013-04-23 13:42:19610 EVERNIA STREET
 PERMIT #13010504
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 SHEET T101: ADD THE FIRE SPRINKLER ENGINEERING
 DOCUMENTS TO THEDRAWING SHEET INDEX.
  
 SHEET FP1- FP12: CORRECT THE SITE ADDRESS FROM 627
 EVERNIA STREET TO 631 EVERNIA STREET.
  
 SHEET FP3: PROVIDE SPRINKLER PROTECTION IN EQUIPMENT
 STORAGE ROOM LOCATED ON POOL DECK.
  
 SHEET FP3: THERE APPEAR TO BE SEVERAL SOFFITS
 OBSTRUCTING SPRINKLER SPRAY IN AND AROUND THE CLUBHOUSE
 AREA. FOR EXAMPLE SPRINKLERS ARE SHOWN 11'-0' AFF IN
 THE LIGHT COVE ADJACENT TO STEPPED CEILINGS OF 10'-0"
 AND 9'-0" AFF. THE SPRINKLER LOCATIONS DO NOT APPEAR TO
 COMPLY WITH OBSTRUCTION TABLE 8.6.5.1.2 (NFPA 13 - 2007
 EDITION).
  
 SHEET FP5: WEST STAIR - IT IS DIFFICULT TO DETERMINE IF
 THE CORRIDOR SPRINKLER WILL PROTECT THE STAIR ENTRY
 VESTIBULE.
  
 SHEET FP12: PROVIDE 2-1/2" FIRE DEPARTMENT STANDPIPE
 HOSE VALVES WITHOUT THE 1-1/2" REDUCER.
  
 FIRE ALARM: PER LOCAL AMENDMENT; DUCT SMOKE DETECTORS
 SHALL INITIATE A GENERAL ALARM IN LIEU OF A SUPERVISORY
 ALARM CONDITION.
  
 SHEET FA2.1: PROVIDE FIRE ALARM ANNUNCIATOR PANEL IN
 LOBBY #001
  
 SHEET FA2.1: PROVIDE NOTIFICATION APPLIANCE IN LAUNDRY
 #015.
  
 SHEET FA4.1: PROVIDE NOTIFICATION APPLIANCE IN COMMON
 LAUNDRY ROOM. TYPICAL EACH FLOOR.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730