2013-04-22 13:28:11 | |
| PERMIT: 13010504 |
| ADD: 631 EVERNIA ST. |
| CONT: KAUFMAN LYNN |
| TEL: (561)361-6700 |
| |
| |
| EVERNIA PLACE |
| AFFORDABLE SENIOR HOUSING |
| |
| 2010 FLORIDA BUILDING CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 3RD REVIEW |
| APRIL 22/ 2013 |
| ACTION: DENIED |
| |
| 4TH REVIEW APRIL 24/2013 |
| |
| 1) 3RD REVIEW IN PROCESS OF UNITY OF TITLE, ENGINEERING |
| WILL NOTIFY ME ONCE THE UNITY OF TITLE HAS BEEN |
| RECORDED. |
| |
| THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE |
| UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE. |
| THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL |
| BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM |
| 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE |
| COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY |
| OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY |
| LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE. |
| SEE WEBSITE FOR APPLICATION: |
| HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP |
| "APPLICATION FOR UNITY OF TITLE" |
| |
| HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45 |
| -38-UNITYOFTITLE3.PDF |
| |
| VINCENT J NOEL |
| SURVEYOR/REAL ESTATE SUPERVISOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET |
| WEST PALM BEACH, FL 33401 |
| PHONE: 494-1040 EXT: 1096 |
| FAX: 494-1116 |
| E-MAIL: [email protected] |
| |
| ********************************************* |
| |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |
| |
| 2) 3RD REQUEST! THIS BUILDING IS CONSIDERED A THRESHOLD |
| BUILDING, (3) SETS OF PLANS, PRODUCT APPROVALS WILL |
| REQUIRED, ONE SET FOR THE SPECIAL INSPECTOR, ONE FOR |
| THE FIELD, AND A COPY WILL BE KEPT ELECTRONICALLY BY |
| THE BUILDING DEPARTMENT, FOR OUR RECORDS. |
| |
| THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 2A) 2ND REQUEST. 109.3.6.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| DOCUMENTS. |
| |
| 2B) 3RD REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT |
| 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| MINIMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| |
| 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT: |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 2D) 3RD REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| PENETRATIONS, FOR WALLS AND CEILINGS. ALL TRADES THAT |
| PENETRATE THE FIRE RATED SLAB WILL NEED TO USE ONE |
| PRODUCT THAT IS TO BE SPECED OUT BY THE DESIGNER OF |
| RECORD, SO ALL PENETRATIONS WILL REQUIRE THE |
| ENGINEERING SHEETS FOR THAT SPECIFIC PRODUCT AND |
| APPLICATION. |
| |
| 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS |
| PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY |
| THE CHIEF BUILDING INSPECTOR KEN CONRAD: |
| |
| PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE |
| (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR |
| AUDITING OF JOBSITE INSPECTIONS. |
| |
| 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB |
| SUMMARY OR HISTORY FOR THIS TYPE OF CONCRETE |
| RESTORATION. THIS MAY BE SUBMITTED TO KEN CONRAD BY |
| E-MAIL. KEN CONRAD: [email protected] |
| |
| 2E)(2) 3RD REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 3) SOILS REPORT BY ARDAMEN 11/19/2012, & 12/27/2012. |
| 2010 FBC-B 1803.2 SOILS INVESTIGATION ARE PROVIDED WILL |
| REQUIRE A PEDS SIGNATURE SINCE THEY ARE SIGNED AND |
| SEALED. |
| |
| 4-5) COMPLIED. |
| |
| 6) 3RD REQUEST 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP) BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 7) 2ND 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.41 COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| CORNELL GAGARGE DOOR PLEASE CIRCLE WHICH TYPE OF DOOR |
| IS TO BE INSTALLED AND ASSOCIATED PRESSURES. |
| |
| (B) WINDOWS/ MULLIONS PLEASE CIRCLE WHICH APPLICATIONS |
| WILL BE USED FOR TYPE OF GLAZING SIZE OF WINDOW AND |
| ASSOCIATED PRESSURES, PLEASE INDICATE IF STEEL |
| RE-INFORCEMENT WILL BE REQUIRED FOR THE ASSOCIATED |
| PRESSUES. |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES ROOFING MEMBRANE |
| COVER SHEET IS ACTUALLY ROOFING INSULATION, NOT THE |
| ROOFING MEMBRANE, NO PRODUCT APPROVAL WAS SUBMITTED FOR |
| THE ROOF COVERING. |
| METAL ROOFING PLEASE CIRCLE WHICH SUB-SYSTEM IS TO BE |
| INSTALLED, AND IF ENHANCED FASTENING WILL BE ALLOWED |
| SEE ALLOWED. NOTE ONLY THE COVER SHEET WAS UPLOADED, |
| NEITHER THE EVALUATION REPORT WAS UPLOADED NOR THE |
| INSTALATION INSTRUCTIONS. |
| (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| STANDS |
| |
| 8) 2COMPLIED. |
| |
| 9) SHEET LS-101: |
| |
| 9A-F) COMPLIED . |
| |
| |
| 10) SHEET A-201: |
| 10A-B) COMPLIED. |
| . |
| 10C) BUILDING PROVISO: TO BE SUPPLIED AS A LOW VOLTAGE |
| PERMIT. PROVIDE COMPLIANCE WITH F] 915.1 GENERAL. |
| EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN |
| ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE |
| PREVENTION CODE. |
| |
| 10D)(1) 3RD REQUEST. MACHINE ROOM-LESS ELEVATORS SHEET |
| A-621. KONE ECOSPACE. WILL NEED MANUFACTURERS |
| REQUIREMENTS FOR INSTALLATION. MAY STILL NEED TO |
| INCORPORATE HOIST WAY VENTING REQUIREMENTS FOUND IN |
| 2010 FBC-B 3004. |
| |
| 10D) (2) COMPLIED. PROVIDE COMPLIANCE WITH 3002.4 |
| ELEVATOR CAR TO ACCOMMODATE AN AMBULANCE STRETCHER. |
| |
| 11) SHEET A202 TRASH CHUTE |
| 11A)3RD REQUEST. SEMI COMPLIED, LS-103/ LS-104. THE |
| NORTH STAIRWELL INDICATES THE TRASH CHUTE ACTUALLY |
| PENETRATING THE 2 HOUR FIRE RATED STAIR ENCLOSURE. |
| PLEASE REVIEW 2010 FBC-B 1022.4 PENETRATIONS INTO & |
| THROUGH AN EXIT ENCLOSURE. PLEASE REVIEW THE |
| REQUIREMENTS FOR TERMINATION ROOM 708.13.4 ALSO SEE |
| 708.8. 708.8 DEALS WITH HOW THE TRASH CHUTE WILL |
| PENETRATE THE 2 HOUR SHAFT.T . |
| |
| 11B) COMPLIED. |
| |
| 11C) COMPLIED. |
| |
| 11D) 4/24/13 COMPLIED. 4TH REVIEW. |
| |
| 11E) 3RD REQUEST. 4/24/2013 4TH REVIEW. SHEET A-601 |
| DETAIL # 1 TRASH CHUTE SHAFT STOPS AT THE BOTTOM OF THE |
| 2ND FLOOR, IT DOES NOT CONTINUE THROUGH TO THE 1ST |
| FLOOR ALTHOUGH THE SHAFT DOES PENETRATE THE 2ND FLOOR |
| ASSEMBLY AND 1ST FLOOR WALL. PLEASE SEE 708.11 |
| ENCLOSURE AT THE BOTTOM . TRASH CHUTE DETAILS WERE |
| UPLOADED AND DEPICT A 2 HR HEAT ACTIVATED ACCORDIAN |
| FIRE DAMPER. PLEASE PROVIDE THE MANUFACTURERS |
| INSTALATION INSTRUCTIONS THAT WILL THE DAMPER TO BE |
| INSTALLED ON A 45 DEGREE ANGLE, IT IS DEPICTED IN THERE |
| LITERATURE AS A HORIZONTAL APPLICATION. |
| |
| 11F) COMPLIED. |
| |
| 11G) 3RD REQUEST. 4TH REVIEW 4/24/13 2010 FBC-B |
| 708.13.6. AUTOMATIC SPRINKLERS SYSTEM. AN APPROVED |
| AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED IN |
| ACCORDANCE WITH SECTION 903.2.11.2. F] 903.2.11.2 |
| RUBBISH AND LINEN CHUTES.BUILDINGS WITH SHUTES GREATER |
| THAN 3 STORIES SHALL HAVE ADDTIONAL HEADS AT |
| ALTERNATING FLOORS. NEITHER THE TRASH CHUTE NOR FIRE |
| SPRINKLER DRAWINGS HAVE ONLY ONE FIRE SPRINKLER HEAD AT |
| THE 3RD FLOOR. |
| 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM |
| SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN |
| CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING |
| THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL |
| SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT |
| ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE |
| FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE |
| FIRE SPRINKLERS. |
| |
| 12) COMPLIED. |
| |
| 13) 2ND REQUEST. SHEET A450 DETAILS 1-3 HAVE GENERAL |
| NOTES, A602, A609, A-620 AT DETAILS INDICATING SOLID |
| SHEATHING THEN NOTES 1 & 2 THE SPECIFIC NOTE INDICATES |
| THE USE OF DENSE-DECK. PLEASE BE AWARE OF PRESSURES |
| FROM THE PRODUCT APPROVAL WILL BE FOR 3/4 INCH OR 5/8 |
| CDX PLYWOOD NOT FOR DENSE DECK, IF PLYWOOD IS USED IT |
| NEEDS TO BE FIRE RETARDENT TREATED PLYWOOD SEE 603.1.1. |
| |
| 4/24/13 NOTE HAVE BEEN CHANGED TO 5/8 INCH CDX PLYWOOD, |
| NO MENTION OF FIRE RETARDENT TREATED PLYWOOD. |
| |
| 13) COMPLIED. |
| |
| 14A) COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16) COMPIED. |
| |
| 17) COMPLIED. |
| |
| 18A-B COMPLIED. |
| |
| 18C) 3RD REQUEST.4TH REVIEW 4/24/13/ PLEASE SHOW |
| COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE |
| SOUND, FLOOR CEILING ASSEMBLIES TO HAVE A INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50, (45 IF FIELD |
| TESTED). THE PLANS DO NOT PROVIDE WHAT FLOOR FINISHES |
| WILL OCCUR IN THTE TENANT SUITES NOR THE COMMON AREAS |
| OR ELECTRICAL ROOMS ... |
| |
| 19) COMPLIED |
| |
| 20)COMPLIED. |
| |
| 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |
| *****INFORMATIONAL*****PLEASE!!!!!!!: WHEN RESUBMITTING |
| PLANS PLEASE INDICATE THE REVISION & REMOVE & REPLACE |
| ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING |
| THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION |
| OF THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |