2013-03-27 11:12:59 | 610 EVERNIA STREET |
| PERMIT #13010504 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| RESPONSE COMMENT (03/27/13): PLEASE PROVIDE A NOTE ON |
| THE PLANS. |
| ORIGINAL COMMENT: ALL CONSTRUCTION WORK SHALL CONFORM |
| TO THE REQUIREMENTS OF NFPA 241. THE FIRE PROTECTION |
| STANDPIPE SYSTEM SHALL BE EXTENDED TO EACH FLOOR AS |
| EACH FLOOR IS CONSTRUCTED. PORTABLE FIRE EXTINGUISHERS |
| SHALL BE LOCATED THROUGHOUT THE CONSTRUCTION AREA. |
| SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| EXTERIOR AREAS. ALL CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED |
| OUTSIDE THE BUILDING, SAFE RECEPTACLES FOR SMOKING |
| MATERIALS SHALL BE PROVIDED. |
| |
| RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION |
| DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE |
| ISSUED. |
| ORIGINAL COMMENT - FOR ISSUANCE OF A GENERAL BUILDING |
| PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING |
| CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION |
| DOCUMENTS FOR THE DESIGN OF 50 OR MORE AUTOMATIC FIRE |
| SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED, |
| THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| FOR A SUB-PERMIT. PER FLORIDA ADMINISTRATIVE CODE |
| SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| RESPONSE COMMENT (03/27/13): ENGINEERED CONTRUCTION |
| DOCUMENTS ARE REQUIRED BEFORE ANY SUB- PERMITS WILL BE |
| ISSUED. |
| ORIGINAL COMMENT - PROVIDE AN AUTOMATIC CLASS I |
| STANDPIPE SYSTEM THROUGHOUT THE BUILDING INCLUDING THE |
| PARKING GARAGE. |
| |
| RESPONSE COMMENT (03/27/13): SHEET A202 STILL INDICATES |
| "TRASH CHUTE THROUGH WALL." |
| ORIGINAL COMMENT - SHEET A202: TRASH CHUTE STAIR |
| PENETRATIONS ARE NOT PERMITTED ON ANY LEVEL PER SECTION |
| 7.1.3.2 (NFPA 101). |
| |
| RESPONSE COMMENT (03/27/13): SEVERAL OF THE DOORS DO |
| NOT INDICATE THE TYPE OF HARDWARE TO BE USED. ON SHEET |
| A-202 FOR EXAMPLE, DOORS LOCATED IN CLUBHOUSE #002 HAVE |
| DOORS #002A (MARK SF-8) AND #002D (MARK F-1) THAT SERVE |
| AN ASSEMBLY USE WITH AN OCCUPANT LOAD EXCEEDING 100 |
| PERSONS BUT THE DOOR SCHEDULE DOES NOT INDICATE THE USE |
| OF PANIC HARDWARE. ANOTHER EXAMPLE IS NORTH STAIR DOOR |
| #002E (MARK SS15) WHERE THE PLAN STATES, "FIRE EXIT |
| HARDWARE" BUT THE DOOR SCHEDULE DOES NOT. ON SHEET |
| A-201, DOOR #G03 (MARK F2) INDICATES PANIC HARDWARE IN |
| THE SCHEDULE BUT THIS IS A FIRE RATED DOOR NEEDING FIRE |
| EXIT HARDWARE. THESE ARE JUST SOME EXAMPLES. PLEASE |
| VERIFY ALL DOORS THROUGHOUT PLANS. |
| REPEAT COMMENT - SHEET A800: FIRE-RATED DOORS SHOULD BE |
| EQUIPPED WITH FIRE EXIT HARDWARE IN LIEU OF THE |
| SPECIFIED PANIC HARDWARE. |
| |
| RESPONSE COMMENT (03/27/13): STILL NO FLOOR DRAIN SHOWN |
| ON SHEET P1.2. |
| REPEAT COMMENT - SHEET P1.2: NO FLOOR DRAIN PROVIDED IN |
| FIRE PUMP ROOM. |
| |
| RESPONSE COMMENT (03/27/13): NON-ESSENTIAL STAIR |
| EQUIPMENT IS STILL SHOWN ON THE PLAN. |
| REPEAT COMMENT - SHEET MEP1.1: STAIR SHAFT PENETRATIONS |
| SHALL BE LIMITED TO EQUIPMENT ESSENTIAL TO THE FUNCTION |
| OF THE STAIR (SPRINKLERS, STANDPIPES, STAIR |
| PRESSURIZATION DUCTS, ETC.) |
| |
| RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1 |
| THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX |
| SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS. |
| ELECTRICAL: NO FIRE ALARM CONSTRUCTION DOCUMENTS COULD |
| BE LOCATED. PROVIDE SPEAKER/STROBE NOTIFICATION |
| APPLIANCES WITH VOICE ANNOUNCEMENTS AND MICROPHONE. |
| PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE |
| NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN |
| THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| |
| RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1 |
| THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX |
| SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS. |
| ELECTRICAL: PROVIDE PHASE 1 RECALL AND PHASE II |
| FIREFIGHTER EMERGENCY OPERATIONS FOR ELEVATORS. PROVIDE |
| SMOKE DETECTION IN ELEVATOR LOBBY AND MACHINE ROOM |
| AREAS. ELEVATOR RECALL SHALL BE INTERFACED WITH FIRE |
| ALARM SYSTEM. |
| |
| RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1 |
| THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX |
| SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS. |
| ELECTRICAL: PLANS DO NOT INDICATE THE METHOD (HEAT |
| DETECTOR/FLOW SWITCH WITHOUT TIME DELAY) USED TO SHUNT |
| TRIP POWER TO THE ELEVATOR IN THE EVENT AN AUTOMATIC |
| SPRINKLER ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| |
| RESPONSE COMMENT (03/27/13): FIRE ALARM DRAWINGS FA1.1 |
| THROUGH FA1.7 WERE NOT SUBMITTED FOR REVIEW. ALSO INDEX |
| SHEET T-101 DOES NOT INDICATE FIRE ALARM DRAWINGS. |
| ELECTRICAL: PROVIDE TAMPER SWITCHES FOR SUPERVISING THE |
| BACKFLOW PREVENTER IN THE OPEN POSITION. |
| |
| WESLEY JOLIN |
| FIRE INVESTIGATOR & INSPECTOR |
| OFFICE OF THE FIRE MARSHAL |
| WEST PALM BEACH FIRE RESCUE |