Plan Review Notes
Plan Review Notes For Permit 13010504
Permit Number 13010504
Review Stop B
Sequence Number 2
Notes
Date Text
2013-03-25 16:35:54 
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2ND REVIEW
 MARCH 25/ 2013
 ACTION: DENIED
  
 1) SEMI-COMPLIED.
  
 THE CIVIL PLAN C-2 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) 2ND REQUEST! THIS BUILDING IS CONSIDERED A THRESHOLD
 BUILDING, (3) SETS OF PLANS, PRODUCT APPROVALS WILL
 REQUIRED, ONE SET FOR THE SPECIAL INSPECTOR, ONE FOR
 THE FIELD, AND A COPY WILL BE KEPT ELECTRONICALLY BY
 THE BUILDING DEPARTMENT, FOR OUR RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONCRETE
 RESTORATION. THIS MAY BE SUBMITTED TO KEN CONRAD BY
 E-MAIL. KEN CONRAD: [email protected]
  
 2E)(2) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) MISSING SOILS REPORT BY ARDAMEN 11/19/2012, &
 12/27/2012. 2010 FBC-B 1803.2 SOILS INVESTIGATION
 REQUIRED.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2ND 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) 2ND REQUEST. FOLDER CONTAINING WALL LOUVER NOA
 11-0408.05 EXPIRED JULY 09/12. CUT SHEET FOR THE RUSKIN
 ACL 12450 LIST A NOA 11-0207.21 BUT NOT PROVIDED.
  
 9) SHEET LS-101:
  
 9A-F) COMPLIED .
  
  
 10) SHEET A-201:
 10A) 2ND REQUEST. IN BOTH STAIRWELLS THE NORTH AND EAST
 CONTINUE BELOW GRADE, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 1022.7 DISCHARGE IDENTIFICATION. A STAIRWAY
 IN AN EXIT ENCLOSURE SHALL NOT CONTINUE BELOW ITS LEVEL
 OF EXIT DISCHARGE UNLESS AN APPROVED BARRIER IS
 PROVIDED AT THE LEVEL OF EXIT DISCHARGE TO PREVENT
 PERSONS FROM UNINTENTIONALLY CONTINUING INTO LEVELS
 BELOW. DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS
 SPECIFIED IN SECTION 1011.
  
 10B) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B: [F] 914.1 SHAFTWAY MARKINGS.
 VERTICAL SHAFTS SHALL BE IDENTIFIED AS REQUIRED BY
 SECTIONS 914.1.1 AND 914.1.2.
  
 [F] 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS.
 OUTSIDE OPENINGS ACCESSIBLE TO THE FIRE DEPARTMENT AND
 THAT OPEN DIRECTLY ON A HOISTWAY OR SHAFTWAY
 COMMUNICATING BETWEEN TWO OR MORE FLOORS IN A BUILDING
 SHALL BE PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED
 LETTERS AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE
 BACKGROUND. SUCH WARNING SIGNS SHALL BE PLACED SO AS TO
 BE READILY DISCERNIBLE FROM THE OUTSIDE OF THE
 BUILDING.
  
 [F] 914.1.2 INTERIOR ACCESS TO SHAFTWAYS.
 DOOR OR WINDOW OPENINGS TO A HOISTWAY OR SHAFTWAY FROM
 THE INTERIOR OF THE BUILDING SHALL BE PLAINLY MARKED
 WITH THE WORD ?SHAFTWAY? IN RED LETTERS AT LEAST 6
 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. SUCH
 WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE.
  
 EXCEPTION: MARKINGS SHALL NOT BE REQUIRED ON SHAFTWAY
 OPENINGS THAT ARE READILY DISCERNIBLE AS OPENINGS ONTO
 A SHAFTWAY BY THE CONSTRUCTION OR ARRANGEMENT.
  
 [F] 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
 10) 2ND REQUEST. SHEET A-201:
 10C) PROVIDE COMPLIANCE WITH F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 10D) MACHINE ROOM-LESS ELEVATORS SHEET A-621. KONE
 ECOSPACE. WILL NEED MANUFACTURERS REQUIREMENTS FOR
 INSTALLATION. MAY STILL NEED TO INCORPORATE HOIST WAY
 VENTING REQUIREMENTS FOUND IN 2010 FBC-B 3004. PROVIDE
 COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE AN
 AMBULANCE STRETCHER.
  
 11) SHEET A202 TRASH CHUTE
 11A) SEMI COMPLIED, LS-103/ LS-104. THE NORTH STAIRWELL
 INDICATES THE TRASH CHUTE ACTUALLY PENETRATING THE 2
 HOUR FIRE RATED STAIR ENCLOSURE. PLEASE REVIEW 2010
 FBC-B 1022.4 PENETRATIONS INTO & THROUGH AN EXIT
 ENCLOSURE. PLEASE REVIEW THE REQUIREMENTS FOR
 TERMINATION ROOM 708.13.4.
  
 11B) SEMI-COMPLIED. LS-103 ? LS-104. THE TRASH CHUTE
 VESTIBULE COMMON TO 2ND- 6TH FLOORS, BEING LOCATED IN A
 VESTIBULE. SHEET LS-103/ LS-104 THE 2010 FBC-B 708.13.3
 REQUIRES REFUSE CHUTES TO HAVE A SEPARATE ACCESS ROOM
 TO BE A 1 HR FIRE BARRIER ENCLOSURE AND 3/4 HR OPENING
 PROTECTIVES. THE LIFE SAFETY SHEETS DO NOT INDICATE A
 3/4 HR RATING ON THE DOOR. 708.13.1 OPENINGS SHALL NOT
 OPEN INTO CORRIDORS. 708.13.1.
  
 11C) 2ND REQUEST LS-103/ LS-104. THE TRASH CHUTE IS
 DEPICTED TO BE IN A RATED SHAFT WITH A A/C DUCT IN THE
 SAME ENCLOSURE. 2010 FBC-B 708.13.1 A SHAFT ENCLOSURE
 CONTAINING A REFUSE CHUTE SHALL NOT BE USED FOR ANY
 OTHER PURPOSE AND SHALL BE ENCLOSED IN ACCORDANCE WITH
 708.4.
  
 11D) 2ND REQUEST. SHEET A-601DETAIL # 1 INDICATES THE
 REFUSE CHUTE GOES THROUGH THE ROOF BUT THE SHAFT
 ENCLOSURE STOPS AT THE CEILING OF THE 6TH FLOOR, PLEASE
 REVIEW 708.12 ENCLOSURES AT THE TOP AND THE REQUIRED
 FIRE RATING OF MATERIALS.
  
 11E) 2ND REQUEST. SHEET A-601 DETAIL # 1 TRASH CHUTE
 SHAFT STOPS AT THE BOTTOM OF THE 2ND FLOOR, IT DOES NOT
 CONTINUE THROUGH TO THE 1ST FLOOR ALTHOUGH THE SHAFT
 DOES PENETRATE THE 2ND FLOOR ASSEMBLY AND 1ST FLOOR
 WALL. PLEASE SEE 708.11 ENCLOSURE AT THE BOTTOM .
  
 11F) 2ND REQUEST. PLEASE PROVIDE MANUFACTURERS SPEC ON
 THE MATERIALS TO BE USED FOR THE REFUSE CHUTE.
 708.13.2.
  
 11G) 2ND REQUEST. 2010 FBC-B 708.13.6. AUTOMATIC
 SPRINKLERS SYSTEM. AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH SECTION
 903.2.11.2. F] 903.2.11.2 RUBBISH AND LINEN CHUTES.
 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN
 CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING
 THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT
 ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE
 FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE
 FIRE SPRINKLERS.
  
 12) 2ND REQUEST. SHEET A-402 DETAILS A-601/ DETAIL # 1,
 A-602 DETAIL # 1 BOTH DEAL WITH ROOFTOP CONSTRUCTION.
 NOTE: METAL SPANISH TILE ROOFING TO BE ATTACHED TO 5/8?
 DENSEDECK WHICH WILL BE SECURED TO THE METAL DECK. NOTE
 THE PRODUCT APPROVALS FOR THE METAL ROOF TILE MAY NOT
 INCLUDE DENSE DECK AS THE DECKING MATERIAL THEY WERE
 TESTED WITH NOR THE METAL B DECK BELOW THAT. IF THAT IS
 THE CASE THE ENGINEER OF RECORD WILL NEED TO PROVIDE
 CALCULATIONS TO RESIST THE MOMENT OF UPLIFT. COMPONENTS
 & CLADDING 1609.6.4.4.1.
  
 13) 2ND REQUEST. SHEET A450 DETAILS 1-3 HAVE GENERAL
 NOTES AT DETAILS INDICATING SOLID SHEATHING THEN NOTES
 1 & 2 THE SPECIFIC NOTE INDICATES THE USE OF
 DENSE-DECK. PLEASE BE AWARE OF PRESSURES FROM THE
 PRODUCT APPROVAL WILL BE FOR 3/4 INCH OR 5/8 CDX
 PLYWOOD NOT FOR DENSE DECK, IF PLYWOOD IS USED IT NEEDS
 TO BE FIRE RETARDENT TREATED PLYWOOD SEE 603.1.1.
  
 13A) 2ND REQUEST. 2010 WPB ADMINISTRATIVE CODE DOES NOT
 ALLOW FOR THE USE OF TERMS SUCH AS ?EQUIVALENT, ? SUCH
 INFORMATION SHALL BE SPECIFIC AND TECHNICAL IN NATURE.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13B) 2ND REQUEST. THIS BUILDING TYPE IS INDICATED AS A
 TYPE I-B BUILDING PLEASE SEE 2010 FBC-B 603.1.1 FIRE
 RETARDANT TREATED WOOD AND ALLOWABLE USES.
  
 13C) 2ND REQUEST. PLEASE BE AWARE OF THE ROOFING
 MATERIALS (PRODUCT APPROVALS) THAT WERE TESTED AN THE
 THICKNESS OF THE ROOF DECKING SHEATHING, AND
 LIMITATIONS SET FORTH IN THE PRODUCT APPROVALS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 14) 2ND REQUEST. SHEET A452 ROOF DETAIL # 1 INDICATES
 THE USE OF LIGHT WEIGHT INSULATING CONCRETE AND THE
 INSULATION BEING TAPERED TO A MINIMAL AMOUNT. 2010
 ENERGY CODE 506.2.1 REQUIRES A MINIMUM OF R-19 FOR
 MULTI-FAMILY RESIDENCES, AS DEPICTED THERE IS LESS THAN
 A R-19 INSULATION AT THE ROOF DRAINS A MINIMUM OF R-19
 INSULATION NOT AN AVERAGE. SEE 2007 BOAF INFORMAL
 INTERPRETATION # 5438. WILL NEED ADDITIONAL INFORMATION
 ON THE LIGHTWEIGHT CONCRETE INSULATION.
  
 15) 2ND REQUEST. A-609 DETAIL # 2 INDICATES THE USE OF
 PRE-MANUFACTURED FOAM FACTORY # 419 TRIM ON THE
 EXTERIOR OF THE BUILDING AT A HEIGHT GREATER THAN 40
 FEET ABOVE GRADE. SEE 2010 FBC-B 1406.2.2 (2).
 COMBUSTIBLE EXTERIOR TRIM.
  
 16) 2ND REQUEST. SHEET A-630 INDICATEES STAIR RAILING
 DETAILS, NONE ARE SHOWN HANDRAILS OR GAURDRAILS. 2010
 FBC-B 1013.3 GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES IN DIAMETER. GAURDRAILS TO
 COMPLY WITH 1013.
  
 17) 2ND REQUEST. SHEET -634 DETAIL # 1 INDICATES THE
 USE OF ICYENE FOAM WALL INSULATION, PLEASE PROVIDE
 TESTING REPORT FOR THE ICYENE SHOWING COMPLIANCE WITH
 FBC-B 2603.4.
  
 18A) 2ND REQUEST, SHEET A-650 P2 PLEASE PROVIDE EITHER
 THE UL LISTING INDICATING THE I HOUR FIRE RATING.
  
 18B) 2ND REQUEST.SHEET A650 P2 INDICATES A STC RATING
 OF 49 FOR UL LISTING # U465, THE 2010 FBC-B 1207.2
 REQUIRES A STC RATING OF 50 (45 IF FIELD TESTED).
  
 18C) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH 2010
 FBC-B 1207.3 STRUCTURE BORNE SOUND, FLOOR CEILING
 ASSEMBLIES TO HAVE A INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50, (45 IF FIELD TESTED).
  
 19)2ND REQUEST A-202 PLAZA DECK, PLEASE SHOW COMPLIANCE
 WITH THE REQUIREMENT 2010 FBC-B 424.1.1 EFFECTIVE
 BARRIER REQUIREMENTS FOR POOLS AND SPAS & 424.1.3.1.9..
  
 20)COMPLIED.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 *****INFORMATIONAL*****PLEASE!!!!!!!: WHEN RESUBMITTING
 PLANS PLEASE INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING
 THE ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION
 OF THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  