Plan Review Notes
Plan Review Notes For Permit 13010504
Permit Number 13010504
Review Stop M
Sequence Number 1
Notes
Date Text
2013-02-06 11:30:21PASS PROVISO
 1) DETAIL # 8 PAGE M0.2 PROVIDE THE BOLT SIZE THAT
 ANCHORS THE CURB TO THE ROOF FROM THE ENGINEER AT ROUGH
 INSPECTION.
 PER SECTION 301.12 FBC (M)
 2) PROVIDE A DETAIL FROM THE ENGINEER ON THE DUCT TO
 STAND AND
 STAND TO ROOF TIE DOWN AT ROUGH INSPECTION .
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 3) IN REGARDS TO PAGE M1.1 REFER TO SECTION 404
 ENCLOSED PARKING GARAGES
 CONCENTRATION OF CARBON MONOXIDE 25 PARTS PER MILLION.
 2010 FBC (M)
 4) PROVIDE THE MANUFACTURERS INSTRUCTIONS FOR THE
 DRYERS AT ROUGH INSPECTION
 PER SECTION 504.6.4.2 FBC (M)
 5) PROVIDE A DUCT SMOKE DETECTOR FOR AHU #2.
 PER SECTION 606.2.1 SUPPLY AIR SYSTEM 2010 FBC (M)
 6) PROVIDE METAL DOORS FOR AHU- 1A AND AHU-1B
 PER SECTION 602.2.1 MATERIALS WITHIN PLENUMS .