2013-02-22 15:22:54 | 13010504 |
| 631 EVERNIA STREET |
| FIVE STORY CONDO |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| E2.3 |
| ILLUMINATION OF THE MEANS OF EGRESS SHALL BE CONTINUOUS |
| DURING THE TIME LIGHTING IS NEEDED. VERIFY THAT ALL |
| REQUIRED EMERGENCY LIGHTING HAS BATTERY BACK UP. FBC |
| 1006.1.2 |
| |
| E3.1 |
| ADDITIONAL RECEPTACLES ARE REQUIRED IN TEH KITCHEN AND |
| AT THE ENTRANCE WALL AREA. NEC 210.52 |
| NOTE 7 IS NOT APPROPRIATE BECAUSE NON METALLIC SHEATHED |
| CABLE IS NOT PERMITTED IN THIS OCCUPANCY. NEC 334.12 |
| |
| E4.1 |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| AND FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. |
| NEC 110.22, 110.16, 110.22 |
| |
| THE RESIDENTIAL 400 AMP METER CENTER APPEARS TO REQUIRE |
| AN ADDITIONAL SET OF FEEDERS. NEC 215.5 |
| |
| PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE PUMP |
| FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL WIRING |
| AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED. |
| INDICATE THE FIRE RATING AND MATERIAL REQUIRED. NEC |
| 695.6, 695.14 |
| |
| VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING |
| NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR, |
| PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE |
| ACCESSORY?S. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT |
| MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN |
| THE MOTOR IS OPERATING AT 115% OF THE FULL ?LOAD |
| CURRENT RATING. NEC 695.6 , 695.7 |
| |
| INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE |
| IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY |
| INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC |
| 700.9 |
| |
| PROVIDE SIGNS AT THE SERVICE INDICATING THE TYPE AND |
| LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC |
| 700.8 |
| |
| PROVIDE PANEL SCHEDULES FOR PANEL P AND PANEL H1A. FBC |
| 107 |
| |
| |