Plan Review Notes
Plan Review Notes For Permit 13010504
Permit Number 13010504
Review Stop B
Sequence Number 1
Notes
Date Text
2013-02-21 16:27:57 
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: KAUFMAN LYNN
 TEL: (561)361-6700
  
  
 EVERNIA PLACE
 AFFORDABLE SENIOR HOUSING
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 1ST REVIEW
 FEB. 14/ 2013
 ACTION: DENIED
  
 1) PLEASE REVIEW THE ADDRESS FOR THIS PROJECT, THE
 CITY?S ADDRESS FOR THIS PCN NUMBER IS 631 EVERNIA WHERE
 AS THE PLANS INDICATE 627 EVERNIA, PLEASE CORRECT THE
 DISCREPANCY. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 THE CIVIL PLAN C-3 APPEARS THAT THE LOTS ARE TO BE
 UNIFIED, A TITLE OF UNITY IS REQUIRED. UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE RECORDED AT THE
 COUNTY COURTHOUSE. SUBMIT A COPY OF THE RECORDED 'UNITY
 OF OF TITLE' DOCUMENT SO THAT FBC TABLE 601 BOUNDARY
 LINE REQUIREMENTS MAY BE DEEMED NOT APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
  
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
  
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
  
 *********************************************
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
 2) THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 (3) SETS OF PLANS, PRODUCT APPROVALS WILL REQUIRED, ONE
 SET FOR THE SPECIAL INSPECTOR, ONE FOR THE FIELD, AND A
 COPY WILL BE KEPT ELECTRONICALLY BY THE BUILDING
 DEPARTMENT, FOR OUR RECORDS.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A WRITTEN STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 2E) A THRESHOLD PLAN REVIEW STOP WILL BE PUT ON THIS
 PROJECT UNTIL THESE ITEMS ARE COMPLETED AS REQUESTED BY
 THE CHIEF BUILDING INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE
 (561) 805-6700) FOR IN-PROGRESS INSPECTIONS FOR
 AUDITING OF JOBSITE INSPECTIONS.
  
 2E)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. THIS MAY
 BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2E)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 3) MISSING SOILS REPORT BY ARDAMEN 11/19/2012, &
 12/27/2012. 2010 FBC-B 1803.2 SOILS INVESTIGATION
 REQUIRED.
  
 4) SHEET S-01 THE WIND DESIGN LIST THIS AS A ?B?
 EXPOSURE. PLEASE REVIEW 2010 FBC-B 1609.4.2 SURFACE
 ROUGHNESS C, THIS SITE MEETS THE REQUIREMENTS OF A C
 EXPOSURE WITH THE WIND DIRECTION FROM THE NW QUADRANT.
 THIS WILL EFFECT THE PRESSURES ILLUSTRATED UNDER THE
 WIND LOAD CHARTS FOR COMPONENTS AND CLADDING.
  
 5) SHEET S-01 WIND LOAD COMPONENTS AND CLADDING CHART.
 PLEASE INCLUDE THE COMPONENTS AND CLADDING PRESSURES
 FOR 10 SQ FT AND 20 SQ FT SINCE THESE WILL BE THE SIZES
 REQUIRED FOR A LOT OF WINDOWS (20 SQ FT) AND 10 SQ FT
 FOR THE ROOF TOP PRESSURES, WE USE THE AREA FOR
 FASTENERS WHICH IS THE 10 SQ FT.
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) FOLDER CONTAINING WALL LOUVER NOA 11-0408.05 EXPIRED
 JULY 09/12. CUT SHEET FOR THE RUSKIN ACL 12450 LIST A
 NOA 11-0207.21 BUT NOT PROVIDED.
  
 9) SHEET LS-101:
 9A) THE SHEET INDICATES G02 TO BE THE FIRE PUMP ROOM
 WITH A PARTIAL 2 HR WALL AROUND THE ROOM PLEASE REVIEW
 2010 FBC-B 913.2.1 PROTECTION OF FIRE PUMP ROOMS ARE TO
 BE COMPLETELY SURROUNDED BY A 2 HOUR WALL, ? SEPARATED
 FROM ALL OTHER AREAS OF THE BUILDING?? PLEASE ALSO
 PROVIDE OPENING PROTECTION FOR THE DOORWAY 2010 FBC-B
 TABLE 715.4.
  
 9) LS-101
  
 9B) SHEET A-201 ALSO INDICATES A PUMP ROOM 020, IS THIS
 A FIRE PUMP ROOM?
  
 9C) THE 2010 FBC-B FIRE PUMP ROOMS 913.2 ARE TO BE
 PROTECTED AGAINST THE INTERRUPTION OF SERVICE AND BE
 PROTECTED IN ACCORDANCE WITH NFPA 20 AGAINST FLOODING.
 WITH THE FIRE PUMP IN THE BASEMENT IF THERE IS A FIRE
 WHERE THE FIRE SPRINKLERS DO GO OFF, WHAT WILL STOP THE
 WATER FROM RISING IN THE FIRE PUMP ROOM.
  
 9D) ROOM G-03 INDICATES THAT IT IS A STORAGE ROOM WHAT
 IS THE PURPOSE OF THIS ROOM? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 9E) THIS SHEET INDICATES STORAGE G04, THE PLANS DO NOT
 INDICATE DOORS INTO THIS SPACE PLEASE PROVIDE
 ADDITIONAL INFORMATION. 107.2.1.3.
  
 9F) THE PLANS INDICATE A LIFT G10 PLEASE PROVIDE
 ADDITIONAL INFORMATION, WHAT WILL THIS LIFT BE USED
 FOR? 107.2.1.3.
  
 10) SHEET A-201:
 10A) IN BOTH STAIRWELLS THE NORTH AND EAST CONTINUE
 BELOW GRADE, PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B
 1022.7 DISCHARGE IDENTIFICATION. A STAIRWAY IN AN EXIT
 ENCLOSURE SHALL NOT CONTINUE BELOW ITS LEVEL OF EXIT
 DISCHARGE UNLESS AN APPROVED BARRIER IS PROVIDED AT THE
 LEVEL OF EXIT DISCHARGE TO PREVENT PERSONS FROM
 UNINTENTIONALLY CONTINUING INTO LEVELS BELOW.
 DIRECTIONAL EXIT SIGNS SHALL BE PROVIDED AS SPECIFIED
 IN SECTION 1011.
  
 10B) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B: [F]
 914.1 SHAFTWAY MARKINGS.
 VERTICAL SHAFTS SHALL BE IDENTIFIED AS REQUIRED BY
 SECTIONS 914.1.1 AND 914.1.2.
  
 [F] 914.1.1 EXTERIOR ACCESS TO SHAFTWAYS.
 OUTSIDE OPENINGS ACCESSIBLE TO THE FIRE DEPARTMENT AND
 THAT OPEN DIRECTLY ON A HOISTWAY OR SHAFTWAY
 COMMUNICATING BETWEEN TWO OR MORE FLOORS IN A BUILDING
 SHALL BE PLAINLY MARKED WITH THE WORD ?SHAFTWAY? IN RED
 LETTERS AT LEAST 6 INCHES (152 MM) HIGH ON A WHITE
 BACKGROUND. SUCH WARNING SIGNS SHALL BE PLACED SO AS TO
 BE READILY DISCERNIBLE FROM THE OUTSIDE OF THE
 BUILDING.
  
 [F] 914.1.2 INTERIOR ACCESS TO SHAFTWAYS.
 DOOR OR WINDOW OPENINGS TO A HOISTWAY OR SHAFTWAY FROM
 THE INTERIOR OF THE BUILDING SHALL BE PLAINLY MARKED
 WITH THE WORD ?SHAFTWAY? IN RED LETTERS AT LEAST 6
 INCHES (152 MM) HIGH ON A WHITE BACKGROUND. SUCH
 WARNING SIGNS SHALL BE PLACED SO AS TO BE READILY
 DISCERNIBLE.
  
 EXCEPTION: MARKINGS SHALL NOT BE REQUIRED ON SHAFTWAY
 OPENINGS THAT ARE READILY DISCERNIBLE AS OPENINGS ONTO
 A SHAFTWAY BY THE CONSTRUCTION OR ARRANGEMENT.
  
 [F] 914.2 EQUIPMENT ROOM IDENTIFICATION.
 FIRE PROTECTION EQUIPMENT SHALL BE IDENTIFIED IN AN
 APPROVED MANNER. ROOMS CONTAINING CONTROLS FOR
 AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS AND VALVES
 OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL
 ELEMENTS SHALL BE IDENTIFIED FOR THE USE OF THE FIRE
 DEPARTMENT. APPROVED SIGNS REQUIRED TO IDENTIFY FIRE
 PROTECTION EQUIPMENT AND EQUIPMENT LOCATION SHALL BE
 CONSTRUCTED OF DURABLE MATERIALS, PERMANENTLY INSTALLED
 AND READILY VISIBLE.
 10) SHEET A-201:
 10C) PROVIDE COMPLIANCE WITH F] 915.1 GENERAL.
 EMERGENCY RESPONDER RADIO COVERAGE SHALL BE PROVIDED IN
 ALL NEW BUILDINGS IN ACCORDANCE THE FLORIDA FIRE
 PREVENTION CODE.
  
 10D) MACHINE ROOM-LESS ELEVATORS SHEET A-621. KONE
 ECOSPACE. WILL NEED MANUFACTURERS REQUIREMENTS FOR
 INSTALLATION. MAY STILL NEED TO INCORPORATE HOIST WAY
 VENTING REQUIREMENTS FOUND IN 2010 FBC-B 3004. PROVIDE
 COMPLIANCE WITH 3002.4 ELEVATOR CAR TO ACCOMMODATE AN
 AMBULANCE STRETCHER.
  
 11) SHEET A202 TRASH CHUTE
 11A) THE NORTH STAIRWELL INDICATES THE TRASH CHUTE
 ACTUALLY PENETRATING THE 2 HOUR FIRE RATED STAIR
 ENCLOSURE. PLEASE REVIEW 2010 FBC-B 1022.4 PENETRATIONS
 INTO & THROUGH AN EXIT ENCLOSURE.
  
 11B) THE TRASH CHUTE VESTIBULE COMMON TO 2ND- 6TH
 FLOORS, BEING LOCATED IN A VESTIBULE. THE 2010 FBC-B
 708.13.3 REQUIRES REFUSE CHUTES TO HAVE A SEPARATE
 ACCESS ROOM TO BE A 1 HR FIRE BARRIER ENCLOSURE AND ?
 HR OPENING PROTECTIVE?S. 708.13.1 OPENINGS SHALL NOT
 OPEN INTO CORRIDORS. 708.13.1.
  
 11C) THE TRASH CHUTE IS DEPICTED TO BE IN A RATED SHAFT
 WITH A A/C DUCT IN THE SAME ENCLOSURE. 2010 FBC-B
 708.13.1 A SHAFT ENCLOSURE CONTAINING A REFUSE CHUTE
 SHALL NOT BE USED FOR ANY OTHER PURPOSE AND SHALL BE
 ENCLOSED IN ACCORDANCE WITH 708.4.
  
 11D) SHEET A-601DETAIL # 1 INDICATES THE REFUSE CHUTE
 GOES THROUGH THE ROOF BUT THE SHAFT ENCLOSURE STOPS AT
 THE CEILING OF THE 6TH FLOOR, PLEASE REVIEW 708.12
 ENCLOSURES AT THE TOP AND THE REQUIRED FIRE RATING OF
 MATERIALS.
  
 11E) SHEET A-601 DETAIL # 1 TRASH CHUTE SHAFT STOPS AT
 THE BOTTOM OF THE 2ND FLOOR, IT DOES NOT CONTINUE
 THROUGH TO THE 1ST FLOOR ALTHOUGH THE SHAFT DOES
 PENETRATE THE 2ND FLOOR ASSEMBLY AND 1ST FLOOR WALL.
 PLEASE SEE 708.11 ENCLOSURE AT THE BOTTOM .
  
 11F) PLEASE PROVIDE MANUFACTURERS SPEC ON THE MATERIALS
 TO BE USED FOR THE REFUSE CHUTE. 708.13.2.
  
 11G) 2010 FBC-B 708.13.6. AUTOMATIC SPRINKLERS SYSTEM.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2. F]
 903.2.11.2 RUBBISH AND LINEN CHUTES.
 2010 FBC-B 903.2.11.2. AN AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP OF RUBBISH AND LINEN
 CHUTES AND IN THEIR TERMINAL ROOMS. CHUTES EXTENDING
 THROUGH THREE OR MORE FLOORS SHALL HAVE ADDITIONAL
 SPRINKLER HEADS INSTALLED WITHIN SUCH CHUTES AT
 ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL BE ACCESSIBLE
 FOR SERVICING. PROVIDE DETAILS FOR THE SERVICING OF THE
 FIRE SPRINKLERS.
  
 12) SHEET A-402 DETAILS A-601/ DETAIL # 1, A-602 DETAIL
 # 1 BOTH DEAL WITH ROOFTOP CONSTRUCTION. NOTE: METAL
 SPANISH TILE ROOFING TO BE ATTACHED TO 5/8? DENSEDECK
 WHICH WILL BE SECURED TO THE METAL DECK. NOTE THE
 PRODUCT APPROVALS FOR THE METAL ROOF TILE MAY NOT
 INCLUDE DENSE DECK AS THE DECKING MATERIAL THEY WERE
 TESTED WITH NOR THE METAL B DECK BELOW THAT. IF THAT IS
 THE CASE THE ENGINEER OF RECORD WILL NEED TO PROVIDE
 CALCULATIONS TO RESIST THE MOMENT OF UPLIFT. COMPONENTS
 & CLADDING 1609.6.4.4.1.
  
 13) SHEET A450 DETAILS 1-3 HAVE GENERAL NOTES AT
 DETAILS INDICATING SOLID SHEATHING THEN NOTES 1 & 2 THE
 SPECIFIC NOTE INDICATES THE USE OF ?? PLYWOOD SHEATHING
 OR EQUIVALENT.
  
 13A) 2010 WPB ADMINISTRATIVE CODE DOES NOT ALLOW FOR
 THE USE OF TERMS SUCH AS ?EQUIVALENT, ? SUCH
 INFORMATION SHALL BE SPECIFIC AND TECHNICAL IN NATURE.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 13B) THIS BUILDING TYPE IS INDICATED AS A TYPE I-B
 BUILDING PLEASE SEE 2010 FBC-B 603.1.1 FIRE RETARDANT
 TREATED WOOD AND ALLOWABLE USES.
  
 13C) PLEASE BE AWARE OF THE ROOFING MATERIALS (PRODUCT
 APPROVALS) THAT WERE TESTED AN THE THICKNESS OF THE
 ROOF DECKING SHEATHING, AND LIMITATIONS SET FORTH IN
 THE PRODUCT APPROVALS.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 14) SHEET A452 ROOF DETAIL # 1 INDICATES THE USE OF
 LIGHT WEIGHT INSULATING CONCRETE AND THE INSULATION
 BEING TAPERED TO A MINIMAL AMOUNT. 2010 ENERGY CODE
 506.2.1 REQUIRES A MINIMUM OF R-19 FOR MULTI-FAMILY
 RESIDENCES, AS DEPICTED THERE IS LESS THAN A R-19
 INSULATION AT THE ROOF DRAINS A MINIMUM OF R-19
 INSULATION NOT AN AVERAGE. SEE 2007 BOAF INFORMAL
 INTERPRETATION # 5438. WILL NEED ADDITIONAL INFORMATION
 ON THE LIGHTWEIGHT CONCRETE INSULATION.
  
 15) A-609 DETAIL # 2 INDICATES THE USE OF
 PRE-MANUFACTURED FOAM FACTORY # 419 TRIM ON THE
 EXTERIOR OF THE BUILDING AT A HEIGHT GREATER THAN 40
 FEET ABOVE GRADE. SEE 2010 FBC-B 1406.2.2 (2).
 COMBUSTIBLE EXTERIOR TRIM.
  
 16) SHEET A-631 DETAIL# 1, A HANDRAIL SECTION /
 GUARDRAIL, THE PLANS INDICATE THE PICKETS TO BE 5
 INCHES ON CENTER AND A 1X1 INCH PICKET. 2010 FBC-B
 1013.3 GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES IN DIAMETER.
  
 17) SHEET -634 DETAIL # 1 INDICATES THE USE OF ICYENE
 FOAM WALL INSULATION, PLEASE PROVIDE TESTING REPORT FOR
 THE ICYENE SHOWING COMPLIANCE WITH FBC-B 2603.4.
  
 18A) SHEET A-650 P2 PLEASE PROVIDE EITHER THE UL
 LISTING INDICATING THE I HOUR FIRE RATING.
  
 18B) SHEET A650 P2 INDICATES A STC RATING OF 49 FOR UL
 LISTING # U465, THE 2010 FBC-B 1207.2 REQUIRES A STC
 RATING OF 50 (45 IF FIELD TESTED).
  
 18C) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1207.3
 STRUCTURE BORNE SOUND, FLOOR CEILING ASSEMBLIES TO HAVE
 A INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50,
 (45 IF FIELD TESTED).
  
 19) A-202 PLAZA DECK, PLEASE SHOW COMPLIANCE WITH THE
 REQUIREMENT 2010 FBC-B 424.1.1 EFFECTIVE BARRIER
 REQUIREMENTS FOR POOLS AND SPAS.
  
 20) SHEET S-01 INDICATES THE WIND EXPOSURE TO BE A ?B?
 EXPOSURE, THE 2010 FBC-B 1609.4.2 SURFACE ROUGHNESS
 WHERE WIND CAN RACE IN ANY QUADRANT 150 WIDE AND 600
 FEET LONG, EXPOSURE C. UPDATE EXPOSURE AND ASSOCIATED
 PRESSURE TABLES.
  
 21) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved