2013-03-25 11:23:03550 SOUTH ROSEMARY AVENUE - SUITE #160
 PERMIT #13010420
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE
 DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE
 EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR
 MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING
 SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH
 REQUESTS MUST BE SUBMITTED IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED
 SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND
 EXISTING PENETRATIONS SHALL BE A APPROPRIATELY
 PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT
 CORRIDOR INDICATING "EXIT CORRIDOR - NO STORAGE OR
 COMBUSTIBLES."
  
 REPEAT COMMENT - SHEET A1.0: ALL EXIT AND EXIT ACCESS
 DOORS TO BE EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE
 INCLUDING EXISTING DOORS LOCATED IN THE REAR EXIT
 ACCESS CORRIDOR ALONG COLUMN LINE "E." DOOR #111 TO BE
 PROVIDED WITH PANIC HARDWARE AS WELL.
  
 NEW COMMENT - SHEET A1.0: MAIN ENTRY #100 AND MAIN
 ENTRY #119 DOORS TO BE EQUIPPED WITH PANIC HARDWARE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730