2013-03-25 11:23:03 | 550 SOUTH ROSEMARY AVENUE - SUITE #160 |
| PERMIT #13010420 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED |
| SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND |
| EXISTING PENETRATIONS SHALL BE A APPROPRIATELY |
| PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT |
| CORRIDOR INDICATING "EXIT CORRIDOR - NO STORAGE OR |
| COMBUSTIBLES." |
| |
| REPEAT COMMENT - SHEET A1.0: ALL EXIT AND EXIT ACCESS |
| DOORS TO BE EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE |
| INCLUDING EXISTING DOORS LOCATED IN THE REAR EXIT |
| ACCESS CORRIDOR ALONG COLUMN LINE "E." DOOR #111 TO BE |
| PROVIDED WITH PANIC HARDWARE AS WELL. |
| |
| NEW COMMENT - SHEET A1.0: MAIN ENTRY #100 AND MAIN |
| ENTRY #119 DOORS TO BE EQUIPPED WITH PANIC HARDWARE. |
| |