Plan Review Notes
Plan Review Notes For Permit 13010420
Permit Number 13010420
Review Stop M
Sequence Number 1
Notes
Date Text
2013-01-22 11:31:55*** CORRECTIONS NEEDED FOR MECHANICAL REVIEW. ***
  
 1) SUBMIT COOLING LOAD CALCULATIONS, PER 2010
 FBC/ENERGY 503.2.1.
  
 2) SHOW ON MECHANICAL PLANS THE DUCT SMOKE DETECTORS AS
 SHOWN ON PLAN FA-1. SEE 2010 FBC/M 606.1.
  
 3) PLEASE STATE IF THE WATER HEATER IN THE DRY STORAGE
 ROOM #129 IS ELECTRIC OR GAS. IF GAS SHOW COMPLIANCE
 WITH 2010 FBC/G 304.1 COMBUSTION AIR.
  
 MECHANICAL PLAN REVIEW BY:
 TOM GORDON (HY-BYRD INC.) (561) 805-6732