Plan Review Notes For Permit 13010420 |
Permit Number |
13010420 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-22 11:31:55 | *** CORRECTIONS NEEDED FOR MECHANICAL REVIEW. *** | | | | 1) SUBMIT COOLING LOAD CALCULATIONS, PER 2010 | | FBC/ENERGY 503.2.1. | | | | 2) SHOW ON MECHANICAL PLANS THE DUCT SMOKE DETECTORS AS | | SHOWN ON PLAN FA-1. SEE 2010 FBC/M 606.1. | | | | 3) PLEASE STATE IF THE WATER HEATER IN THE DRY STORAGE | | ROOM #129 IS ELECTRIC OR GAS. IF GAS SHOW COMPLIANCE | | WITH 2010 FBC/G 304.1 COMBUSTION AIR. | | | | MECHANICAL PLAN REVIEW BY: | | TOM GORDON (HY-BYRD INC.) (561) 805-6732 |
|