2013-01-22 09:34:15 | 550 SOUTH ROSEMARY AVENUE ? SUITE #160 |
| PERMIT #13010420 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| DEMOLITION: FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE |
| DURING DEMOLITION AND RENOVATION ACTIVITIES. IN THE |
| EVENT A FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR |
| MORE THAN 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING |
| SHALL BE PLACED UNDER A FIRE WATCH. ALL FIRE WATCH |
| REQUESTS MUST BE SUBMITTED IN WRITING (FAX: |
| 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| SHEET LS1.0: EXISTING REAR EXIT ACCESS CORRIDOR NEEDED |
| SOME WORK DURING LAST ROUTINE FIRE INSPECTION. NEW AND |
| EXISTING PENETRATIONS SHALL BE A APPROPRIATELY |
| PROTECTED. PROVIDE PERMANENT SIGNAGE THROUGHOUT |
| CORRIDOR INDICATING ?EXIT CORRIDOR ? NO STORAGE OR |
| COMBUSTIBLES.? |
| |
| SHEET LS1.0: PROVIDE HANDRAILS ON BOTH SIDES OF STAIRS |
| AT KJ BOOTH #104 AND MB CONTROL #112. HANDRAILS SHALL |
| BE LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 |
| INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED |
| VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE |
| OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE |
| WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS. |
| HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT |
| LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. |
| |
| SHEET A1.0: ALL EXIT AND EXIT ACCESS DOORS TO BE |
| EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE INCLUDING |
| EXISTING DOORS LOCATED IN THE REAR EXIT ACCESS CORRIDOR |
| ALONG COLUMN LINE ?E.? DOOR #111 TO BE PROVIDED WITH |
| PANIC HARDWARE AS WELL. |
| |
| SHEET FA-1: PROVIDE SPEAKER/STROBE NOTIFICATION |
| APPLIANCES AS NEW ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM |
| NOTIFICATION BY VISIBLE SIGNALS AND VOICE |
| ANNOUNCEMENTS. PROVIDE FIRE ALARM MICROPHONE NEAR |
| ANUNCIATOR PANEL. PROVIDE A PRE-RECORDED FIRE ALARM |
| EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| AND EXIT THE BUILDING IMMEDIATELY. MUSIC SHALL SHUT |
| DOWN UPON ACTIVATION OF FIRE ALARM SYSTEM TO ALLOW FIRE |
| ALARM MESSAGE TO BE INTELLIGIBLE. |
| |
| SHEET FA-1: NO FIRE ALARM NOTIFICATION APPLIANCES |
| LOCATED IN KITCHEN PREP AREA OR OUTDOOR DINING AREA |
| #118. |
| |
| SHEET FA-1: APPEAR TO HAVE INSUFFICIENT NUMBER OF |
| NOTIFICATION APPLIANCES NEAR MECHANICAL BULL AREA |
| #113/BAR #2. |
| |
| SHEET FS-1: CONSTRUCTION DOCUMENTS ESTABLISH BEN ELLIS |
| AS ENGINEER OF RECORD; THEREFORE, FIRE SPRINKLER SHOP |
| DRAWINGS AND HYDRAULIC CALCULATIONS SHALL NOT BE SIGNED |
| AND SEALED BY THE CONTRACTOR PER FLORIDA STATUTE 633. |
| |
| SHEET FS-2: PROVIDE SPRINKLER PROTECTION IN WALK-IN |
| BEER COOLER #110. |
| |