2013-02-12 12:41:21 | 13010420 | | 550 S. ROSEMARY AVE #160 | | TEQUILA COWBOY AND WANNABE?S | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED | | TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE PANEL | | BOARDS. NEC 314.28 | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | AND FOR THE MAIN DISCONNECTING MEANS. NEC 110.22, | | 110.16, 110.22 | | | | PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE | | WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC | | ENERGY CONSERVATION 505.3 | | | | PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING | | SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS. | | INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL | | SUPPORT DETAIL FOR WALL OR CEILING MOUNTED | | TRANSFORMERS. NEC 110.26, 240.24 | | | | VERIFY SERVICE CAPACITY FROM THE MAIN SERVICE FOR THIS | | OCCUPANCY BY CALCULATION. INCLUDE EXISTING AND | | POTENTIAL FUTURE OCCUPANCY LOADS WHICH WILL BE SUPPLIED | | FROM THE EXISTING SERVICE. NEC 215.2 | | | | | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|