Plan Review Notes
Plan Review Notes For Permit 13010420
Permit Number 13010420
Review Stop E
Sequence Number 1
Notes
Date Text
2013-02-12 12:41:2113010420
 550 S. ROSEMARY AVE #160
 TEQUILA COWBOY AND WANNABE?S
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 INDICATE THE APPROPRIATE SIZE FOR THE PULL BOX INTENDED
 TO HOUSE THE MAIN FEEDER CONDUCTORS TO THE PANEL
 BOARDS. NEC 314.28
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 AND FOR THE MAIN DISCONNECTING MEANS. NEC 110.22,
 110.16, 110.22
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 PROVIDE SAFE WORKING CLEARANCES AND DEDICATED WORKING
 SPACE AT ALL ELECTRICAL PANEL BOARDS AND TRANSFORMERS.
 INDICATE LOCATION OF TRANSFORMERS. PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR WALL OR CEILING MOUNTED
 TRANSFORMERS. NEC 110.26, 240.24
  
 VERIFY SERVICE CAPACITY FROM THE MAIN SERVICE FOR THIS
 OCCUPANCY BY CALCULATION. INCLUDE EXISTING AND
 POTENTIAL FUTURE OCCUPANCY LOADS WHICH WILL BE SUPPLIED
 FROM THE EXISTING SERVICE. NEC 215.2
  
  
  