2013-01-31 08:25:15 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1-4. OK | | | | 5. SEE FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1. | | COMPONENTS BEING CHANGED ARE TO MEET THE REQUIREMENTS | | OF FBC 2010 ENERGY CONSERVATION CHAPTER 4 WHEN THE | | ESTIMATED COST EXCEEDS 30 PERCENT OF THE ASSESSED VALUE | | OF THE STRUCTURE. | | | | 2ND REVIEW, NOT ADDRESSED. THIS IS PROVIDED FROM THE | | MANUFACTURER. | | | | NEW COMMENTS: | | | | HORIZONTAL ROLLER METHOD OF INSTALLATION PROPOSED | | (-60PSF) DOES NOT COMPLY WITH DESIGN PRESSURES | | SPECIFIED BY ENGINEER (-60.9). EITHER REVISE THE DESIGN | | PRESSURES OR THE PRODUCT APPROVAL WILL BE REDLINED FOR | | YOU TO INDICATE A METHOD OF INSTALLATION WHICH MEETS | | -63PSF. | | | | PLEASE SEND PRIVATE PROVIDER'S RESUME TO KEN CONRAD AT | | [email protected]. | | | | | | | | |
|