2013-01-24 12:19:21 | 13010418 | | 227 ELWA PLACE | | SF REMODEL | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | ELECTRICAL REVIEW COMMENTS. | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH | | CIRCUIT. NEC 210.11 (C) (3) | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|