2013-01-22 09:39:10 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. REVISE FLOOR PLAN TO INCLUDE ROOM DESIGNATIONS. |
| THERE IS A NOTE ON SHEET A1 THAT EMERGENCY ESCAPE AND |
| RESCUE OPENINGS (FOR SLEEPING ROOMS) TO COMPLY WITH FBC |
| 1029 (SEE ALSO FBC R310). |
| |
| 2. REVISE FLOOR PLAN TO INCLUDE HORIZONTAL ROLLER |
| CONFIGURATIONS AND SINGLE HUNG CONFIGURATIONS OR REVISE |
| WINDOW SCHEDULE TO INCLUDE THIS INFORMATIN (**SLEEPING |
| ROOMS ONLY**). FOR INSTANCE, SEE OPENING O. THE WINDOW |
| WIDTH EXCEEDS MAX FOR AN XO WINDOW, SEE SHEET 4, BUT |
| NOT CLEAR WHETHER AN XOX (DETAIL B OR C) WILL MEET |
| MINIMUM EGRESS WIDTH. SEE ALSO SHEET 4 OF SINGLE HUNG |
| PRODUCT APPROVAL. |
| |
| 3. A2, WINDOW BUCK DETAIL, SPECIFICATION PROPOSES A 1X3 |
| BEVELED BUCK. THIS CONFLICTS WITH THE GRAPHIC AND FBC R |
| 612.10.2.1 WHICH REQUIRES FULL SUPPORT OF THE WINDOW |
| UNLESS OTHERWISE TESTED. |
| |
| 4. DELEGATED ENGINEERING TO BE REVIEWED BY ENGINEER OF |
| RECORD, FS471, FAC61G15 (WINDOW DESIGN PRESSURE |
| ENGINEERING AND FLOOR PLAN). |
| |
| 5. SEE FBC 2010 ENERGY CONSERVATION, TABLE 101.4.1. |
| COMPONENTS BEING CHANGED ARE TO MEET THE REQUIREMENTS |
| OF FBC 2010 ENERGY CONSERVATION CHAPTER 4 WHEN THE |
| ESTIMATED COST EXCEEDS 30 PERCENT OF THE ASSESSED VALUE |
| OF THE STRUCTURE. |
| |
| |