Plan Review Notes For Permit 13010354 |
Permit Number |
13010354 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-22 10:54:36 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. PROVIDE MORE INFORMATION REGARDING USAGE OF SPACE | | AND FLOOR PLAN. INCLUDE EXISTING EXITS, DISTANCE TO | | EXITS, SQUARE FOOT AREA, ETC. (LIFE SAFETY PLAN). NOTE | | THAT THERE IS NO PROVISION FOR BLOCKING EXITS WITH | | HURRICANE SHUTTERS IN THE FBC. | | | | FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF | | EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE | | INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS | | OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. | | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH | | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY | | THIS CHAPTER. | | | | FLOOR PLAN MAY BE SUBMITTED VIA EMAIL. | | |
|