Plan Review Notes For Permit 13010310 |
Permit Number |
13010310 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-02-11 17:34:36 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. OK | | | | 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER | | SHEET FOR THE DOOR, FAC 9N-3. WWW.FLORIDBUILDING.ORG | | | | 2ND REVIEW, NOT PROVIDED. A RESPONSE THAT THIS IS | | EXISTING WITH A LABEL WAS GIVEN, BUT A CURRENT PRODUCT | | APPROVAL IS REQUIRED. EVALUATION REPORT WAS PROVIDED | | FIRST REVIEW, BUT NOT THE COVER SHEET. | | | | 3. OK | | | | 4. OK | | | | 5. THE PRODUCT APPROVAL FOR THE SHUTTERS IS A 2007 | | APPROVAL; 2010 REQUIRED FAC9N-3. | | | | 2ND REVIEW, 2010 PRODUCT APPROVAL PROVIDED, BUT THE | | SHEETS WHICH GIVE THE INSTALLATION INSTRUCTIONS (AND | | ANCHOR SPACING) WERE NOT PROVIDED. PLEASE SUBMIT. | | | | 6. PROVIDE A DETAIL FOR THE HANDRAIL FBC RESIDENTIAL | | 311.7.7. | | | | 2ND REVIEW, A RAILING DETAIL WAS PROVIDED; IS THE | | APPLICATION INCORRECT, AND A RAILING TO BE REEPAIRED, | | NOT A HANDRAIL? | | | | | | | | |
|