Plan Review Notes For Permit 13010305 |
Permit Number |
13010305 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-28 08:34:07 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE | | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER | | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. | | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET | | AT | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | INSTALLATION.PDF | | | | A SCHEDULE WAS PROVIDED BUT IS LACKING SOME INFORMATION | | SUCH AS EDGE DISTANCE, ANCHOR SPACING, PANEL | | ORIENTATION, ETC. IT IS ACCEPTABLE TO USE AN ALTERNATE | | FORM IF IT CONTAINS ALL INFORMATION REQUIRED TO | | DETERMINE WHETHER OR NOT THE PROPOSED INSTALLATION | | COMPLIES WITH THE REQUIREMENTS OF THE PRODUCT APPROVAL. | | | | IF PANELS ARE INSTALLED HORIZONTALLY, PLEASE NOTE THAT | | THE SUBSTRATE WOULD BE CONCRETE BLOCK RATHER THAN | | CONCRETE (GROUTED CELLS) UNLESS YOU HAVE EVIDENCE THAT | | ALL OPENINGS HAVE FORMED AND POURED COLUMNS ON EACH | | SIDE OR WAS CONSTRUCTED OF CONCRETE PANELS. | | | | 2. THIS PARCEL APPEARS TO BE LOCATED IN EXPOSURE D, SEE | | FBC RESIDENTIAL 301. | | |
|