2013-01-14 15:50:16BUILDING PLAN REVIEW
 PERMIT: 13010283
 ADD: 1043 21ST ST
 CONT: MEGATREND INC.
 TEL: (305)613-2287
  
 2010 FLORIDARESIDENTIAL CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 JAN. 14/ 2011
 ACTION: DENIED
  
 1) THE PERSON RESPONSIBLE FOR THE CONSTRUCTION DRAWING
 DESIGN IS TO SIGN THEIR NAME, PRINT THEIR NAME AND
 LICENSE NUMBER ON THE PLANS. 107.1 WPB 2010
 ADMINISTRATIVE CODE.
  
 2) MISSING DESIGN CRITERIA. 107.2.1.2 2010 WPB
 ADMINISTRATIVE CODE. FOR ROOF ASSEMBLIES REQUIRED BY
 THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND
 CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT
 BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST
 BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS.
 PLEASE PROVIDE TO WHAT WIND SPEED AND BUILDING RISK
 CATEGORY THIS BUILDING IS BEING DESIGNED FOR?
  
 3) 2010- R301.2.1.1 DESIGN CRITERIA.
 IN REGIONS WHERE THE ULTIMATE DESIGN WIND SPEEDS, VULT,
 FROM FIGURE R301.2(4) EQUAL OR EXCEED 115 MILES PER
 HOUR (45 M/S) THE DESIGN OF BUILDINGS SHALL BE IN
 ACCORDANCE WITH ONE OF THE FOLLOWING METHODS. THE
 ELEMENTS OF DESIGN NOT ADDRESSED BY THOSE DOCUMENTS IN
 ITEMS 1 THROUGH 8 SHALL BE IN ACCORDANCE WITH THIS
 CODE.
  
 3.1. AMERICAN FOREST AND PAPER ASSOCIATION (AF&PA) WOOD
 FRAME CONSTRUCTION MANUAL FOR ONE- AND TWO-FAMILY
 DWELLINGS (WFCM).
  
 3.2. INTERNATIONAL CODE COUNCIL (ICC) STANDARD FOR
 RESIDENTIAL CONSTRUCTION IN HIGH WIND REGIONS
 (ICC-600).
  
 3.3. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
 STRUCTURES (ASCE-7).
  
 3.4. AMERICAN IRON AND STEEL INSTITUTE (AISI), STANDARD
 FOR COLD-FORMED STEEL FRAMING?PRESCRIPTIVE METHOD FOR
 ONE- AND TWO-FAMILY DWELLINGS (AISI S230).
  
 3.5. CONCRETE CONSTRUCTION SHALL BE DESIGNED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS CODE.
  
 3.6. THE MAF GUIDE TO CONCRETE MASONRY RESIDENTIAL
 CONSTRUCTION IN HIGH WIND AREAS SHALL BE PERMITTED FOR
 APPLICABLE CONCRETE MASONRY BUILDINGS WHERE VASD,
 DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 DOES
 NOT EXCEED 130 MPH (58 M/S) IN EXPOSURE B AND 110 MPH
 (49 M/S) IN EXPOSURE C IN ACCORDANCE WITH FIGURE
 R301.2(4).
  
 3.7. THE APPLICABLE AF&PA WFCM GUIDE TO WOOD
 CONSTRUCTION IN HIGH WIND AREAS SHALL BE PERMITTED FOR
 APPLICABLE WOOD-FRAME BUILDINGS IN REGIONS WHERE VASD,
 DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 DOES
 NOT EXCEED 130 MPH (58 M/S) IN EXPOSURE B.
  
 3.8. STRUCTURAL INSULATED PANEL (SIP) WALLS SHALL BE
 DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CODE.
  
 THE WIND SPEEDS IN FIGURE R301.2(4) SHALL BE CONVERTED
 TO NOMINAL WIND SPEEDS, VASD, IN ACCORDANCE WITH
 SECTION R301.2.1.3 WHEN THE PROVISIONS OF THE STANDARDS
 REFERENCED IN EXCEPTIONS 1 THROUGH 8 ARE USED UNLESS
 THE WIND PROVISIONS IN THE STANDARDS ARE BASED ON
 ULTIMATE WIND SPEEDS AS SPECIFIED IN FIGURE R301.2(4)
 OR CHAPTER 26 OF ASCE 7.
  
 4) THE PLANS DO NOT PROVIDE WHAT THE CLEAR SPAN IS FOR
 THE FRAMING MEMBERS, NOR DOES THE PLANS PROVIDE WHAT
 TYPE OF SPECIES OF WOOD, GRADE OF SPECIES WILL BE USED
 FOR THE FRAMING OF THE RAFTERS OR THE RIDGE BOARD.
 PLEASE PROVIDE THE LENGTH OF THE OVER HANGS FOR ALL
 SIDES OF THE GARAGE.
  
 5) THE PLANS DO NOT PROVIDE THE MAGNITUDE OF FORCES TO
 BE RESISTED, UPLIFT, LATERALL AND GRAVITY LOADS SEE
 TABLE R802.1.9 SEE FOOTNOTES A-F.
  
 6) PLANS DO NOT INDICATE IF CEILING JOIST ARE GOING TO
 BE INSTALLED OR IF WIND TIES WILL BE USED INSTEAD OF
 CEILING JOIST? PLANS SHOW A TYPICAL RAFTER CONNECTION
 TO A HIP BUT NO DETAIL FOR THE RIDGE AND COMMON RAFTER
 CONNECTION, PLEASE PROVIDE THE CORRECT APPLICATION TYPE
 CONNECTION AND SIZE FOR THE FRAMING MEMBER WITH WITH
 THE MANUFACTURERS ALLOWABLE UPLIFTS FOR SAID CONNECTION
 NOR THE WALL CONNECTION, TYPE OF CONNECTION, ALLOWABLE
 UPLIFTS .2010 R802.1.6.5, 1072.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 7) PLANS FAIL TO PROVIDE GABLE END DESIGN INFORMATION
 FOR THE GABLE END WALL, BLOCK, WOOD FRAME, ARE GABLES
 DROPPED GABLE ENDS, PROVIDE CONNECTOR TYPES AND SPACING
 OF FRAMING MEMBERS AND FRAMING SIZES? ADDITIONAL
 INFORMATION REQUIRED. 107.2.1.3.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved