2013-01-14 15:50:16 | BUILDING PLAN REVIEW |
| PERMIT: 13010283 |
| ADD: 1043 21ST ST |
| CONT: MEGATREND INC. |
| TEL: (305)613-2287 |
| |
| 2010 FLORIDARESIDENTIAL CODE W |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| JAN. 14/ 2011 |
| ACTION: DENIED |
| |
| 1) THE PERSON RESPONSIBLE FOR THE CONSTRUCTION DRAWING |
| DESIGN IS TO SIGN THEIR NAME, PRINT THEIR NAME AND |
| LICENSE NUMBER ON THE PLANS. 107.1 WPB 2010 |
| ADMINISTRATIVE CODE. |
| |
| 2) MISSING DESIGN CRITERIA. 107.2.1.2 2010 WPB |
| ADMINISTRATIVE CODE. FOR ROOF ASSEMBLIES REQUIRED BY |
| THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, |
| DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, |
| MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| PLEASE PROVIDE TO WHAT WIND SPEED AND BUILDING RISK |
| CATEGORY THIS BUILDING IS BEING DESIGNED FOR? |
| |
| 3) 2010- R301.2.1.1 DESIGN CRITERIA. |
| IN REGIONS WHERE THE ULTIMATE DESIGN WIND SPEEDS, VULT, |
| FROM FIGURE R301.2(4) EQUAL OR EXCEED 115 MILES PER |
| HOUR (45 M/S) THE DESIGN OF BUILDINGS SHALL BE IN |
| ACCORDANCE WITH ONE OF THE FOLLOWING METHODS. THE |
| ELEMENTS OF DESIGN NOT ADDRESSED BY THOSE DOCUMENTS IN |
| ITEMS 1 THROUGH 8 SHALL BE IN ACCORDANCE WITH THIS |
| CODE. |
| |
| 3.1. AMERICAN FOREST AND PAPER ASSOCIATION (AF&PA) WOOD |
| FRAME CONSTRUCTION MANUAL FOR ONE- AND TWO-FAMILY |
| DWELLINGS (WFCM). |
| |
| 3.2. INTERNATIONAL CODE COUNCIL (ICC) STANDARD FOR |
| RESIDENTIAL CONSTRUCTION IN HIGH WIND REGIONS |
| (ICC-600). |
| |
| 3.3. MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER |
| STRUCTURES (ASCE-7). |
| |
| 3.4. AMERICAN IRON AND STEEL INSTITUTE (AISI), STANDARD |
| FOR COLD-FORMED STEEL FRAMING?PRESCRIPTIVE METHOD FOR |
| ONE- AND TWO-FAMILY DWELLINGS (AISI S230). |
| |
| 3.5. CONCRETE CONSTRUCTION SHALL BE DESIGNED IN |
| ACCORDANCE WITH THE PROVISIONS OF THIS CODE. |
| |
| 3.6. THE MAF GUIDE TO CONCRETE MASONRY RESIDENTIAL |
| CONSTRUCTION IN HIGH WIND AREAS SHALL BE PERMITTED FOR |
| APPLICABLE CONCRETE MASONRY BUILDINGS WHERE VASD, |
| DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 DOES |
| NOT EXCEED 130 MPH (58 M/S) IN EXPOSURE B AND 110 MPH |
| (49 M/S) IN EXPOSURE C IN ACCORDANCE WITH FIGURE |
| R301.2(4). |
| |
| 3.7. THE APPLICABLE AF&PA WFCM GUIDE TO WOOD |
| CONSTRUCTION IN HIGH WIND AREAS SHALL BE PERMITTED FOR |
| APPLICABLE WOOD-FRAME BUILDINGS IN REGIONS WHERE VASD, |
| DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 DOES |
| NOT EXCEED 130 MPH (58 M/S) IN EXPOSURE B. |
| |
| 3.8. STRUCTURAL INSULATED PANEL (SIP) WALLS SHALL BE |
| DESIGNED IN ACCORDANCE WITH THE PROVISIONS OF THIS |
| CODE. |
| |
| THE WIND SPEEDS IN FIGURE R301.2(4) SHALL BE CONVERTED |
| TO NOMINAL WIND SPEEDS, VASD, IN ACCORDANCE WITH |
| SECTION R301.2.1.3 WHEN THE PROVISIONS OF THE STANDARDS |
| REFERENCED IN EXCEPTIONS 1 THROUGH 8 ARE USED UNLESS |
| THE WIND PROVISIONS IN THE STANDARDS ARE BASED ON |
| ULTIMATE WIND SPEEDS AS SPECIFIED IN FIGURE R301.2(4) |
| OR CHAPTER 26 OF ASCE 7. |
| |
| 4) THE PLANS DO NOT PROVIDE WHAT THE CLEAR SPAN IS FOR |
| THE FRAMING MEMBERS, NOR DOES THE PLANS PROVIDE WHAT |
| TYPE OF SPECIES OF WOOD, GRADE OF SPECIES WILL BE USED |
| FOR THE FRAMING OF THE RAFTERS OR THE RIDGE BOARD. |
| PLEASE PROVIDE THE LENGTH OF THE OVER HANGS FOR ALL |
| SIDES OF THE GARAGE. |
| |
| 5) THE PLANS DO NOT PROVIDE THE MAGNITUDE OF FORCES TO |
| BE RESISTED, UPLIFT, LATERALL AND GRAVITY LOADS SEE |
| TABLE R802.1.9 SEE FOOTNOTES A-F. |
| |
| 6) PLANS DO NOT INDICATE IF CEILING JOIST ARE GOING TO |
| BE INSTALLED OR IF WIND TIES WILL BE USED INSTEAD OF |
| CEILING JOIST? PLANS SHOW A TYPICAL RAFTER CONNECTION |
| TO A HIP BUT NO DETAIL FOR THE RIDGE AND COMMON RAFTER |
| CONNECTION, PLEASE PROVIDE THE CORRECT APPLICATION TYPE |
| CONNECTION AND SIZE FOR THE FRAMING MEMBER WITH WITH |
| THE MANUFACTURERS ALLOWABLE UPLIFTS FOR SAID CONNECTION |
| NOR THE WALL CONNECTION, TYPE OF CONNECTION, ALLOWABLE |
| UPLIFTS .2010 R802.1.6.5, 1072.1.3 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 7) PLANS FAIL TO PROVIDE GABLE END DESIGN INFORMATION |
| FOR THE GABLE END WALL, BLOCK, WOOD FRAME, ARE GABLES |
| DROPPED GABLE ENDS, PROVIDE CONNECTOR TYPES AND SPACING |
| OF FRAMING MEMBERS AND FRAMING SIZES? ADDITIONAL |
| INFORMATION REQUIRED. 107.2.1.3. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |
| |