Text |
2013-09-12 17:51:04 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| ICYNENE SPRAY FOAM INSULATION. FBCR 316.3 |
| |
| 2) THE ROOF PLAN ON SHEET A-3 SPECIFIES A POLYGLASS |
| SELF ADHERED ROOF SYSTEM AND A BASE SHEET FASTENING. |
| RAS 117 CALCULATIONS FOR A GAF MODIFIED ROOF SYSTEM ( |
| NOA #09-0224.01 ) WERE SUBMITTED WITHOUT THE PRODUCT |
| APPROVALS WHICH ARE REQUIRED BY DCA RULE 9N-3. IF THE |
| GAF SYSTEM WILL BE INSTALLED REMOVE THE NOTES FOR THE |
| POLYGLASS SYSTEM FROM THE ROOF PLAN AND SUBMIT THE GAF |
| PRODUCT APPROVALS WITH THE APPROVED ASSEMBLY IDENTIFIED |
| AND THAT HAVE BEEN REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD. |
| |
| 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE |
| BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD |
| FOR THE CEMENT PANEL SIDING, THE TRANSOM WINDOWS (AS |
| SHOWN ON THE FLOOR PLANS ON A-1), THE STRUCTURAL WINDOW |
| MULLIONS, BARREL TILE ROOFING AND THE FRONT ENTRY DOOR |
| AS REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENT |
| 107.3.4.1 |
| |
| 4) THERE ARE STILL CONFLICTING NOTES ON THE PLANS IN |
| REGARDS TO THE CEMENT PANEL SIDING AND STUCCO OVER |
| METAL LATH AND PLYWOOD. SEE FRONT ELEVATION ON A-1 AND |
| SHEET A-3 AND CLOUDED NOTE ON RIGHT ELEVATION ON SHEET |
| A-1. PLEASE CORRECT. CITY AMENDMENT 107.2.1.3 |
| |
| 5) PROVIDE STRUCTURAL DETAILS FOR THE PATIO ROOF ABOVE |
| THE DOUBLE FRENCH DOORS. SPECIFY ALL CONNECTORS AND |
| ATTACHMENTS REQUIRED TO PROVIDE SUPPORT AND A |
| CONTINUOUS LOAD PATH. FBCR 301.1 AND 301.2.1 |
| |
| 6) SPECIFY THE CONNECTORS THAT WILL BE USED TO TIE ALL |
| OF THE PARAPET FRAMING TOGETHER AND PROVIDE A |
| CONTINUOUS LOAD PATH.FBCR 301.1 AND 301.2.1 |
| |
| 7) SPECIFY THE ATTACHMENT AND CONNECTORS THAT WILL BE |
| USED TO ATTACH THE 2 X 4 ROOF RAFTER FRAMING TO THE |
| CONTAINERS. FBCR 301.1 AND 301.2.1 |
| |
| 8) SHEET A-1 HAS WHITE-OUT CORRECTION FLUID ON THE |
| RIGHT ELEVATION DETAIL. WHITE-OUT SHOULD NOT BE USED TO |
| MAKE CORRECTIONS TO SIGNED AND SEALED DRAWINGS |
| SUBMITTED FOR PUBLIC RECORD. FS 471 AND CITY AMENDMENTS |
| 107.2.1.4 |
| |
| 9) THE DESIGN PRESSURES FOR THE FRONT DOOR ON SHEET A-1 |
| WERE NOT CORRECTED AND ARE TOO HIGH. FBCR 301.2.1 AND |
| TABLE 301.2(2). |
| |
| 10) PROVIDE A DETAIL THAT SPECIFIES THE ATTACHMENT OF |
| THE GUARD RAIL AT THE BALCONY TO THE STRUCTURE. FBCR |
| 301.1 |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |