2013-09-12 17:51:042010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 ICYNENE SPRAY FOAM INSULATION. FBCR 316.3
  
 2) THE ROOF PLAN ON SHEET A-3 SPECIFIES A POLYGLASS
 SELF ADHERED ROOF SYSTEM AND A BASE SHEET FASTENING.
 RAS 117 CALCULATIONS FOR A GAF MODIFIED ROOF SYSTEM (
 NOA #09-0224.01 ) WERE SUBMITTED WITHOUT THE PRODUCT
 APPROVALS WHICH ARE REQUIRED BY DCA RULE 9N-3. IF THE
 GAF SYSTEM WILL BE INSTALLED REMOVE THE NOTES FOR THE
 POLYGLASS SYSTEM FROM THE ROOF PLAN AND SUBMIT THE GAF
 PRODUCT APPROVALS WITH THE APPROVED ASSEMBLY IDENTIFIED
 AND THAT HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD.
  
 3) SUBMIT TWO COPIES OF PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD
 FOR THE CEMENT PANEL SIDING, THE TRANSOM WINDOWS (AS
 SHOWN ON THE FLOOR PLANS ON A-1), THE STRUCTURAL WINDOW
 MULLIONS, BARREL TILE ROOFING AND THE FRONT ENTRY DOOR
 AS REQUIRED BY DCA RULE 9N-3 AND CITY AMENDMENT
 107.3.4.1
  
 4) THERE ARE STILL CONFLICTING NOTES ON THE PLANS IN
 REGARDS TO THE CEMENT PANEL SIDING AND STUCCO OVER
 METAL LATH AND PLYWOOD. SEE FRONT ELEVATION ON A-1 AND
 SHEET A-3 AND CLOUDED NOTE ON RIGHT ELEVATION ON SHEET
 A-1. PLEASE CORRECT. CITY AMENDMENT 107.2.1.3
  
 5) PROVIDE STRUCTURAL DETAILS FOR THE PATIO ROOF ABOVE
 THE DOUBLE FRENCH DOORS. SPECIFY ALL CONNECTORS AND
 ATTACHMENTS REQUIRED TO PROVIDE SUPPORT AND A
 CONTINUOUS LOAD PATH. FBCR 301.1 AND 301.2.1
  
 6) SPECIFY THE CONNECTORS THAT WILL BE USED TO TIE ALL
 OF THE PARAPET FRAMING TOGETHER AND PROVIDE A
 CONTINUOUS LOAD PATH.FBCR 301.1 AND 301.2.1
  
 7) SPECIFY THE ATTACHMENT AND CONNECTORS THAT WILL BE
 USED TO ATTACH THE 2 X 4 ROOF RAFTER FRAMING TO THE
 CONTAINERS. FBCR 301.1 AND 301.2.1
  
 8) SHEET A-1 HAS WHITE-OUT CORRECTION FLUID ON THE
 RIGHT ELEVATION DETAIL. WHITE-OUT SHOULD NOT BE USED TO
 MAKE CORRECTIONS TO SIGNED AND SEALED DRAWINGS
 SUBMITTED FOR PUBLIC RECORD. FS 471 AND CITY AMENDMENTS
 107.2.1.4
  
 9) THE DESIGN PRESSURES FOR THE FRONT DOOR ON SHEET A-1
 WERE NOT CORRECTED AND ARE TOO HIGH. FBCR 301.2.1 AND
 TABLE 301.2(2).
  
 10) PROVIDE A DETAIL THAT SPECIFIES THE ATTACHMENT OF
 THE GUARD RAIL AT THE BALCONY TO THE STRUCTURE. FBCR
 301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714