2013-03-25 11:18:16 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) PLUMBING RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | THE DIAGRAM SHOWS A SINK ON THE SECOND FLOOR AND A | | DOUBLE LAVATORY AT THE FIRST FLOOR BATHROOM. PLEASE | | CORRECT. | | | | 2) THE BATHROOM GROUP ON THE LOWER FLOOR ARE NOT | | PROPERLY VENTED. THE VERTICAL WET VENT IS ONLY | | PERMITTED TO VENT A COMBINATION OF FIXTURES LOCATED ON | | THE SAME FLOOR LEVEL PER FBCR P3108.4. ALSO SEE P3109.2 | | A VERTICAL WASTE STACK VENT CAN NOT RECEIVE THE | | DISCHARGE OF WATER CLOSETS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|