Plan Review Notes
Plan Review Notes For Permit 13010222
Permit Number 13010222
Review Stop P
Sequence Number 2
Notes
Date Text
2013-03-25 11:18:162010 FBC
  
 DENIED BY PLUMBING
  
 1) PLUMBING RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 THE DIAGRAM SHOWS A SINK ON THE SECOND FLOOR AND A
 DOUBLE LAVATORY AT THE FIRST FLOOR BATHROOM. PLEASE
 CORRECT.
  
 2) THE BATHROOM GROUP ON THE LOWER FLOOR ARE NOT
 PROPERLY VENTED. THE VERTICAL WET VENT IS ONLY
 PERMITTED TO VENT A COMBINATION OF FIXTURES LOCATED ON
 THE SAME FLOOR LEVEL PER FBCR P3108.4. ALSO SEE P3109.2
 A VERTICAL WASTE STACK VENT CAN NOT RECEIVE THE
 DISCHARGE OF WATER CLOSETS.
  