Plan Review Notes For Permit 13010222 |
Permit Number |
13010222 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2013-01-15 15:59:52 | 2010 FBC | | | | DENIED BY PLUMBING | | | | 1) PLUMBING RISER DIAGRAM DOES NOT MATCH FLOOR PLAN. | | THE DIAGRAM SHOWS TWO LAVATORIES AND NO KITCHEN SINK ON | | THE LOWER FLOOR. PLEASE CORRECT. | | | | 2) THE FIXTURES ON THE LOWER FLOOR ARE NOT VENTED. THE | | VERTICAL WET VENT IS ONLY PERMITTED TO VENT A | | COMBINATION OF FIXTURES LOCATED ON THE SAME FLOOR LEVEL | | PER FBCR P3108.4. | | | | 3) THE KITCHEN SINK ON THE UPPER FLOOR CAN NOT TIE INTO | | THE VERTICAL WET VENT FOR THE BATHROOM GROUP. THE WATER | | CLOSET IS REQUIRED TO BE THE LOWEST CONNECTION TO THE | | VERTICAL WET-VENTED SECTION PER FBCR P3108.4. | | THEREFORE, THE HORIZONTAL BRANCH FOR THE KITCHEN SINK | | IS REQUIRED TO CONNECT TO THE VERTICAL DRAIN BELOW THE | | WATER CLOSET. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|