Plan Review Notes
Plan Review Notes For Permit 13010222
Permit Number 13010222
Review Stop P
Sequence Number 1
Notes
Date Text
2013-01-15 15:59:522010 FBC
  
 DENIED BY PLUMBING
  
 1) PLUMBING RISER DIAGRAM DOES NOT MATCH FLOOR PLAN.
 THE DIAGRAM SHOWS TWO LAVATORIES AND NO KITCHEN SINK ON
 THE LOWER FLOOR. PLEASE CORRECT.
  
 2) THE FIXTURES ON THE LOWER FLOOR ARE NOT VENTED. THE
 VERTICAL WET VENT IS ONLY PERMITTED TO VENT A
 COMBINATION OF FIXTURES LOCATED ON THE SAME FLOOR LEVEL
 PER FBCR P3108.4.
  
 3) THE KITCHEN SINK ON THE UPPER FLOOR CAN NOT TIE INTO
 THE VERTICAL WET VENT FOR THE BATHROOM GROUP. THE WATER
 CLOSET IS REQUIRED TO BE THE LOWEST CONNECTION TO THE
 VERTICAL WET-VENTED SECTION PER FBCR P3108.4.
 THEREFORE, THE HORIZONTAL BRANCH FOR THE KITCHEN SINK
 IS REQUIRED TO CONNECT TO THE VERTICAL DRAIN BELOW THE
 WATER CLOSET.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]