2013-01-16 15:16:45 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE PLANS APPEAR TO SHOW TWO SEPARATE UNITS EACH |
| WITH IT'S OWN KITCHEN. FBCR 302.3 REQUIRES ONE HOUR |
| FIRE-RESISTANCE BETWEEN THE TWO UNITS. SHOW COMPLIANCE. |
| |
| 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE |
| STRUCTURE. SHOW COMPLIANCE WITH FBC ENERGY CONSERVATION |
| SECTION 401.2. |
| |
| 3) THE MEAN ROOF HEIGHT FOR THE STRUCTURE IS 20 FEET |
| PER THE PLANS. PLEASE INCREASE THE OPENING PRESSURES TO |
| CORRESPOND WITH THE 20 FT MRH. FBCR 301.2.1 |
| |
| 4) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE |
| PROTECTION. |
| |
| 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| ICYNENE SPRAY FOAM INSULATION. FBCR316.3 |
| |
| 6) PROVIDE A DETAIL SHOWING HOW THE FLOOR ASSEMBLY |
| ABOVE THE COVERED ENTRY WILL BE INSULATED. FBC ENERGY |
| CONSERVATION AND CITY AMENDMENTS 107.2.1 |
| |
| 7) THE NOA NUMBERS LISTED IN THE WINDOW AND DOOR |
| SCHEDULES ON SHEET A-1 DO NOT MATCH THE ONES ON THE |
| PRODUCT APPROVALS THAT WERE SUBMITTED. PLEASE CORRECT. |
| CITY AMENDMENTS 107.2.1 AND DCA RULE 9N-3 |
| |
| 8) SPECIFY HOW THE BASE OF THE 4 X 4 POSTS SUPPORTING |
| THE BALCONY WILL BE ANCHORED TO THE CONCRETE |
| FOUNDATION. FBCR 301.1 |
| |
| 9) SPECIFY HOW THE BALCONY IS ATTACHED TO THE |
| STRUCTURE. CITY AMENDMENTS 107.2.1.3 |
| |
| 10) THE FRONT ELEVATION ON A-1 SPECIFIES A 6 X 6 POST |
| AT THE BALCONY. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 |
| |
| 11) SHOW THAT THE SPIRAL STAIRS COMPLY WITH FBCR |
| 311.7.9.1. |
| |
| 12) THE TYPICAL FRAME DETAIL ON A-1 APPEARS TO SHOW |
| THAT THE END OF THE SHIPPING CONTAINERS WHERE THE DOORS |
| HAVE BEEN REMOVED WILL BE FRAMED WITH 2 X 2 X 1/4" |
| STEEL. PLEASE CLARIFY. ALSO CLARIFY HOW THESE WILL BE |
| WELDED TO THE STRUCTURE AND HOW THE CORRUGATED STEEL |
| SKIN WILL BE ATTACHED TO THE FRAMING. PLEASE BE |
| SPECIFIC. CITY AMENDMENTS 107.2.1 |
| |
| 13) PROVIDE COMPLETE DETAILS OF THE FRAMING AT THE |
| WINDOW AND DOOR OPENINGS AT RIGHT AND LEFT ELEVATIONS. |
| FBCR 301.1 AND CITY AMENDMENTS 107.2.1 |
| |
| 14) INDICATE THE TYPE OF ROOF COVERING THAT WILL BE |
| USED AND SUBMIT PRODUCT APPROVALS FOR IT. FBCR 903.1 |
| |
| 15) INDICATE HOW THE PLUMBING VENT ROOF PENETRATIONS |
| THROUGH THE CORRUGATED STEEL WILL BE FLASHED. FBCR |
| 903.2 |
| |
| 16) SHOW COMPLIANCE WITH FBCR 318.6 FOR REQUIRED |
| GUTTERS AND DOWNSPOUTS ON BUILDINGS WITH EAVES WITH |
| LESS THAN 6 INCH PROJECTIONS. |
| |
| 17) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| HARDI-PLANK SIDING AND THE COMPOSITE DECKING AS |
| REQUIRED BY DCA RULE 9N-3. |
| |
| 18) PROVIDE A STRUCTURAL ANALYSIS THAT INDICATES THE |
| UPPER STORAGE CONTAINER CAN BE CANTILEVERED AS |
| INDICATED ON THE PLANS. CITY AMENDMENTS 107.2.1.3 |
| |