2013-01-10 14:07:034431 EMBARCADERO DRIVE
 PERMIT #13010221
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****CHANGE OF OCCUPANCY FROM BUSINESS TO
 EDUCATIONAL****
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EXIT
 ILLUMINATION, EMERGENCY LIGHTING, TRAVEL DISTANCES,
 COMMON PATH OF TRAVEL ETC.
  
 EXIT ACCESS CORRIDORS SHALL BE A MINIMUM OF 6 FEET IN
 WIDTH AND SHALL HAVE A 1-HOUR FIRE RESISTANCE RATING.
  
 THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY.
 INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE
 (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1
 OF NFPA 101 FLORIDA EDITION 2009.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 ENGINEERED FIRE ALARM CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER
 THAN NORMAL TO THE GENERAL OCCUPANCY (EDUCATIONAL) OF
 THE BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS
 WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF
 CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST
 45-MINUTES PER SECTION 8.7 OF NFPA 101.
  
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
  
 FOR EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED
 ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9
 OF NFPA 101 FLORIDA EDITION 2009.
  
 EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE
 PREVENTION CODE - NFPA 101.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INDICATE IF ANY COOKING IS PLANNED AT THIS LOCATION.
 COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE
 WITH NFPA 96.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 DUE TO THE LACK OF PLAN INFORMATION, A THOROUGH AND
 COMPLETE FIRE REVIEW CANNOT BE COMPLETED AT THIS TIME.
  