2013-01-10 14:07:03 | 4431 EMBARCADERO DRIVE |
| PERMIT #13010221 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ****CHANGE OF OCCUPANCY FROM BUSINESS TO |
| EDUCATIONAL**** |
| |
| DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA |
| FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF |
| BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| |
| PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES, |
| OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EXIT |
| ILLUMINATION, EMERGENCY LIGHTING, TRAVEL DISTANCES, |
| COMMON PATH OF TRAVEL ETC. |
| |
| EXIT ACCESS CORRIDORS SHALL BE A MINIMUM OF 6 FEET IN |
| WIDTH AND SHALL HAVE A 1-HOUR FIRE RESISTANCE RATING. |
| |
| THE BUILDING IS FUNCTIONING AS A MULTIUSE OCCUPANCY. |
| INDICATE IF THE BUILDING IS DESIGNED FOR MIXED USE |
| (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.2.1 |
| OF NFPA 101 FLORIDA EDITION 2009. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| ENGINEERED FIRE ALARM CONSTRUCTION DOCUMENTS ARE |
| REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE ALARM SYSTEM. |
| |
| ANY AREA (STORAGE) HAVING A DEGREE OF HAZARD GREATER |
| THAN NORMAL TO THE GENERAL OCCUPANCY (EDUCATIONAL) OF |
| THE BUILDING, SHALL BE SEPARATED FROM NON-STORAGE AREAS |
| WITH A 1-HOUR FIRE-RATED BARRIER. DOORS SHALL BE SELF |
| CLOSING, POSITIVE LATCHING, AND FIRE-RATED FOR AT LEAST |
| 45-MINUTES PER SECTION 8.7 OF NFPA 101. |
| |
| EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM |
| OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. |
| EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO |
| PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN |
| AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN |
| 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT |
| FLOOR LEVEL. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| |
| FOR EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF |
| 100 OR MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED |
| ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| PANIC HARDWARE. |
| |
| DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, |
| OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| EGRESS SIDE. |
| |
| INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY |
| LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A |
| LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE |
| RELEASED FROM THE EGRESS SIDE OF THE DOOR. |
| |
| THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL |
| OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING |
| OPERATION. THE RELEASING MECHANISM SHALL HAVE AN |
| OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED |
| UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE |
| SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND |
| SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| TWISTING OF THE WRIST TO OPERATE PER SECTION 7.2.1.5.9 |
| OF NFPA 101 FLORIDA EDITION 2009. |
| |
| EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED |
| WITH SIGNS OR STENCILING READING FIRE/SMOKE |
| BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT |
| LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. |
| IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON |
| CENTER. REFERENCE SECTION 8.3.2.4 OF FLORIDA FIRE |
| PREVENTION CODE - NFPA 101. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| INDICATE IF ANY COOKING IS PLANNED AT THIS LOCATION. |
| COOKING OPERATIONS SHALL BE PROTECTED IN ACCORDANCE |
| WITH NFPA 96. |
| |
| ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| AREA. |
| |
| AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| BUILDING PRIOR TO OCCUPANCY. |
| |
| EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| |
| DUE TO THE LACK OF PLAN INFORMATION, A THOROUGH AND |
| COMPLETE FIRE REVIEW CANNOT BE COMPLETED AT THIS TIME. |
| |