Plan Review Notes
Plan Review Notes For Permit 13010221
Permit Number 13010221
Review Stop E
Sequence Number 1
Notes
Date Text
2013-01-10 16:36:1813010221
 4431 EMBARCADERO DRIVE.
 CHANGE OF OCCUPANCY FROM B TO E
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS. DUE TO THE LACK OF DETAIL THIS REVIEW
 IS SUBSTANTIALLY INCOMPLETE.
  
 PROVIDE TWO SETS OF LEGIBLE PLANS FROM A REGISTERED
 DESIGN PROFESSIONAL SHOWING COMPLIANCE WITH THE CODE.
 FBC 107.1
  
 INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE
 EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT
 CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE
 FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH
 PROTECTION, HIGH-LEG MARKING, AND THE MAIN
 DISCONNECTING MEANS.
 NEC 110.22, 110.16, 110.22
  
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC
 250.20
  
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. NEC 230.2, 230.71
  
 PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS.
 INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE
 EQUIPMENT. NEC 210.3, 215.2, 220.40, 230.31, 408.4
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS.
 NEC 422.52
  
 VENDING MACHINES SHALL BE PROTECTED WITH GFCI S. NEC
 422.51
  
 ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST
 BE GFCI PROTECTED. NEC 210.8
  
 PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE
 WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC
 ENERGY CONSERVATION 505.3
  
 VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL,
 UNIFORMITY, BRIGHTNESS AND GLARE IN
 CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7
  
 A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A
 SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS
 REQUIRED. NFPA 101 15.3.4, FBC 907
  
 NOTE:
 SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE,
 DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING.
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  