2013-01-10 16:36:18 | 13010221 |
| 4431 EMBARCADERO DRIVE. |
| CHANGE OF OCCUPANCY FROM B TO E |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| REVIEW COMMENTS. DUE TO THE LACK OF DETAIL THIS REVIEW |
| IS SUBSTANTIALLY INCOMPLETE. |
| |
| PROVIDE TWO SETS OF LEGIBLE PLANS FROM A REGISTERED |
| DESIGN PROFESSIONAL SHOWING COMPLIANCE WITH THE CODE. |
| FBC 107.1 |
| |
| INDICATE THE FAULT CURRENT CAPABILITY OF THE SERVICE |
| EQUIPMENT AND PANEL BOARDS. VERIFY THE EQUIPMENT FAULT |
| CURRENT RATING IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE |
| FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC 110.9 |
| |
| PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH |
| PROTECTION, HIGH-LEG MARKING, AND THE MAIN |
| DISCONNECTING MEANS. |
| NEC 110.22, 110.16, 110.22 |
| |
| SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC |
| 250.20 |
| |
| VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND |
| GROUPED IN ONE LOCATION. NEC 230.2, 230.71 |
| |
| PROVIDE PANEL BOARD SCHEDULES SHOWING BALANCED LOADS. |
| INCLUDE A SUMMARY LOAD CALCULATION FOR THE SERVICE |
| EQUIPMENT. NEC 210.3, 215.2, 220.40, 230.31, 408.4 |
| |
| AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN |
| SERVICE GROUND. NEC 250.94 |
| |
| GFCI PROTECTION IS REQUIRED FOR ELECTRIC WATER COOLERS. |
| NEC 422.52 |
| |
| VENDING MACHINES SHALL BE PROTECTED WITH GFCI S. NEC |
| 422.51 |
| |
| ALL RECEPTACLES LOCATED WITHIN SIX FEET OF A SINKS MUST |
| BE GFCI PROTECTED. NEC 210.8 |
| |
| PROVIDE A LIGHTING DENSITY SUMMARY SHOWING COMPLIANCE |
| WITH THE FLORIDA BUILDING ENERGY CODE REQUIREMENTS. FBC |
| ENERGY CONSERVATION 505.3 |
| |
| VERIFY COMPLIANCE WITH REQUIRED ILLUMINATION LEVEL, |
| UNIFORMITY, BRIGHTNESS AND GLARE IN |
| CLASSROOMS/INSTRUCTION SPACES. FBC 443.3.7 |
| |
| A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A |
| SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS |
| REQUIRED. NFPA 101 15.3.4, FBC 907 |
| |
| NOTE: |
| SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR VOICE, |
| DATA, FIRE ALARM, SECURITY, SIGNAGE, AND SITE LIGHTING. |
| |
| ROBERT LECKY |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |