Notes
Date Text
2013-01-09 16:49:162010 FBC
  
 DENIED BY BUILDING
  
 1) THE SELECTED ROOFING SYSTEM ON PAGE 6 OF NOA NUMBER
 10-0330.02 HAS A MAXIMUM DESIGN PRESSURE OF -45 PSF.
 THE STRUCTURE IS LOCATED ON THE INTER-COASTAL WATERWAY
 IN EXPOSURE CATEGORY D WITH A 170 MPH WIND-SPEED.
 BECAUSE THE REQUIRED UPLIFT PRESSURES EXCEED THE DESIGN
 PRESSURE, RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 IS REQUIRED BY LIMITATION NUMBER 7 OF THE NOA.
 LIMITATION NUMBER 7 ON PAGE 11 OF THE NOA, REQUIRES THE
 CALCULATIONS TO BE PREPARED, SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]