 PERMIT #13010184
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THEMODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 EACH FIRE RATED BARRIER SHALL BE PERMANENTLY IDENTIFIED
 WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-ROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  