2013-02-28 10:45:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FBC 1603.4.1, INCLUDE WIND DESIGN CRITERIA.
  
 NOT ADDRESSED.
  
 2. FOR THE FOUNDATION, PROVIDE CALCULATION TO SHOW THAT
 THE 12X12 FOOTING IS ADEQUATE FOR THE 6' WALL TO RESIST
 WIND LOADS.
  
 2ND REVIEW, FOUNDATION SIZE INCREASED AND APPEARS CODE
 COMPLIANT. HOWEVER, THE NEW PLAN DOES NOT INCLUDE THE
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN FBC 107.
  