Plan Review Notes
Plan Review Notes For Permit 13010045
Permit Number 13010045
Review Stop B
Sequence Number 2
Notes
Date Text
2013-01-16 17:59:54**INFORMATION MAY BE RESUBMITTED VIA EMAIL**
  
 ****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW EXISTING CONDITIONS
 (TYPE OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC
 1029, FBC EXISTING BUILDING 2010 604.1, FBC 1609 AS
 REQUESTED IN PREVIOUS REVIEW. THE CLEAR OPENING CANNOT
 BE REDUCED BY MORE THAN 5%.
  
 REVISE THE FLOOR PLAN TO SHOW INTERIOR WALLS FOR
 BEDROOMS. IT IS NOT CLEAR WHETHER SOME UNITS ARE
 EFFICIENCIES OR ONE BEDROOM UNITS.
  
 STAIR LOCATIONS NOT SHOWN. IT IS NOT CLEAR WHETHER THE
 OPENINGS WITHIN 10' OF THE STAIRS ARE TO BE FIRE RATED.
 "STAIR" WAS WRITTEN ON THE PLAN WITH NO OTHER
 INFORMATION. PROVIDE A PLAN VIEW AND ELEVATIONS IF
 NECESSARY; ALL INFORMATION REQUIRED IN ORDER TO
 DEMONSTRATE CODE COMPLIANCE.
  
 NOT ENOUGH INFORMATION PROVIDED BY CONTRACTOR TO
 DETERMINE CODE COMPLIANCE OR TO PROVIDE A COMPREHENSIVE
 CHECKLIST.
  
 2. PROVIDE BUILDING HEIGHT SO WIND LOAD DESIGN
 PRESSURES CAN BE DETERMINED, FBC 1609.
  
  
  
  
  