Plan Review Notes For Permit 13010045 |
Permit Number |
13010045 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2013-01-16 17:59:54 | **INFORMATION MAY BE RESUBMITTED VIA EMAIL** | | | | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. REVISE THE FLOOR PLAN TO SHOW EXISTING CONDITIONS | | (TYPE OF WINDOW) AND OPENING SIZE FOR BEDROOMS, FBC | | 1029, FBC EXISTING BUILDING 2010 604.1, FBC 1609 AS | | REQUESTED IN PREVIOUS REVIEW. THE CLEAR OPENING CANNOT | | BE REDUCED BY MORE THAN 5%. | | | | REVISE THE FLOOR PLAN TO SHOW INTERIOR WALLS FOR | | BEDROOMS. IT IS NOT CLEAR WHETHER SOME UNITS ARE | | EFFICIENCIES OR ONE BEDROOM UNITS. | | | | STAIR LOCATIONS NOT SHOWN. IT IS NOT CLEAR WHETHER THE | | OPENINGS WITHIN 10' OF THE STAIRS ARE TO BE FIRE RATED. | | "STAIR" WAS WRITTEN ON THE PLAN WITH NO OTHER | | INFORMATION. PROVIDE A PLAN VIEW AND ELEVATIONS IF | | NECESSARY; ALL INFORMATION REQUIRED IN ORDER TO | | DEMONSTRATE CODE COMPLIANCE. | | | | NOT ENOUGH INFORMATION PROVIDED BY CONTRACTOR TO | | DETERMINE CODE COMPLIANCE OR TO PROVIDE A COMPREHENSIVE | | CHECKLIST. | | | | 2. PROVIDE BUILDING HEIGHT SO WIND LOAD DESIGN | | PRESSURES CAN BE DETERMINED, FBC 1609. | | | | | | | | | | |
|