2013-01-08 15:10:41 | 2010 FBC |
| |
| DENIED BY ELECTRIC |
| |
| PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| ELECTRICAL REVIEW COMMENTS. |
| |
| |
| REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| |
| 1) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| |
| 2) ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| GENERAL PURPOSE OUTLETS. NEC 210.12 |
| |
| 3) GFCI PROTECTION IS REQUIRED FOR ALL BATHROOM |
| RECEPTACLES. NEC 210.8 |
| |
| 4) A GFCI PROTECTED RECEPTACLE IS REQUIRED AT THE FRONT |
| AND REAR OF DWELLING UNITS. NEC 210.52 (E) |
| |
| 5) THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH |
| CIRCUIT. NEC 210.11 (C) (3) |
| |
| 6) A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT |
| THE FRONT AND BACK ENTRANCE AREA. NEC 210.70, 230.72 |
| |
| 7) ADD SWITCHES AND RECEPTACLES AS REQUIRED. NEC 210.52 |
| |
| 8) AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET |
| IS REQUIRED IN EVERY HABITABLE ROOM AND BATHROOM. NEC |
| 210.70 (A)(1) |
| |
| 9) AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET |
| IS REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES |
| OR EXISTS WITH GRADE LEVEL ACCESS. |
| |