Plan Review Notes
Plan Review Notes For Permit 13010044
Permit Number 13010044
Review Stop E
Sequence Number 1
Notes
Date Text
2013-01-08 15:10:412010 FBC
  
 DENIED BY ELECTRIC
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 1) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 2) ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS. NEC 210.12
  
 3) GFCI PROTECTION IS REQUIRED FOR ALL BATHROOM
 RECEPTACLES. NEC 210.8
  
 4) A GFCI PROTECTED RECEPTACLE IS REQUIRED AT THE FRONT
 AND REAR OF DWELLING UNITS. NEC 210.52 (E)
  
 5) THE NEW BATHROOM REQUIRES A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
  
 6) A GFCI PROTECTED RECEPTACLE IS REQUIRED OUTSIDE AT
 THE FRONT AND BACK ENTRANCE AREA. NEC 210.70, 230.72
  
 7) ADD SWITCHES AND RECEPTACLES AS REQUIRED. NEC 210.52
  
 8) AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET
 IS REQUIRED IN EVERY HABITABLE ROOM AND BATHROOM. NEC
 210.70 (A)(1)
  
 9) AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING OUTLET
 IS REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES
 OR EXISTS WITH GRADE LEVEL ACCESS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]