2013-01-04 08:28:19****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FBC 301, 1609, RESISTANCE TO WIND LOADS:
  
 1. THE ENGINEERING PROVIDED REFERS TO ASCE7-05 AND NOA
 07-1018.10. PLEASE UPDATE; CURRENT REFERENCE IS
 ASCE7-10 AND THE NOA SUBMITTED IS 12-0516.13.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471. PLEASE SUBMIT ORIGINAL ENGINEERING.
  
 3. THE LETTER OF AUTHORIZATION FROM THE PROPERTY OWNER
 IS NOT NOTARIZED. PLEASE PROVIDE A NOTARIZED LETTER OR
 HAVE THE OWNER SIGN THE PERMIT APPLICAITON.
  