 771 W. EXECUTIVE CENTER DRIVE
 COMMERCIAL RENOVATION
 TEMPORARY FIRE STATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS SERVING SLEEPING AREAS. NEC
 210.18
 GFCI PROTECTION IS REQUIRED FOR ALL OUTDOOR
 RECEPTACLES. NEC 210.8 (B)
 GFCI PROTECTION IS REQUIRED FOR THE CORD REEL. NEC
 210.8 (B)
 GFCI PROTECTION IS REQUIRED FOR ALL BATHROOM
 RECEPTACLES. NEC 210.8 (B)
  