Plan Review Notes For Permit 12120699 |
Permit Number |
12120699 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2014-06-30 11:52:03 | 2010 FBC | | | | TRUSS DRAWINGS ARE DENIED | | | | 1) THE DESIGNER OF RECORD FOR THE STRUCTURE HAS | | INDICATED THAT THE TRUSS LAYOUT AND DRAWINGS FOR THE | | MODEL E HIP OPTION DO NOT MATCH THE STRUCTURAL PLANS. | | THE FRAMING AT THE FRONT PORCH IS DIFFERENT THAN THE | | PLANS. | | | | 2) THE TRUSS DRAWINGS FOR THE MODEL E GABLE OPTION DO | | NOT HAVE THE DESIGNER OF RECORDS SHOP REVIEW STAMP ON | | THEM. THEY WILL NEED TO BE REVIEWED BY THE D.O.R. IT | | APPEARS THAT THE TRUSS LAYOUT AND DRAWINGS FOR THIS | | OPTION DOES NOT MATCH THE STRUCTURAL PLANS. THE TRUSS | | DRAWINGS HAVE A TWO PLY GIRDER (B5) NEAR THE FRONT | | PORCH AND THE STRUCTURAL DRAWING SHOW THE TRUSSES | | BEARING ON THE EXTERIOR WALL. | | | | 3) THE TRUSS LAYOUT PLANS ARE NOT SIGNED AND SEALED BY | | THE TRUSS ENGINEER. FS 471 & FAC 61G-31.003 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|