Plan Review Notes
Plan Review Notes For Permit 12120699
Permit Number 12120699
Review Stop B
Sequence Number 5
Notes
Date Text
2014-06-30 11:52:032010 FBC
  
 TRUSS DRAWINGS ARE DENIED
  
 1) THE DESIGNER OF RECORD FOR THE STRUCTURE HAS
 INDICATED THAT THE TRUSS LAYOUT AND DRAWINGS FOR THE
 MODEL E HIP OPTION DO NOT MATCH THE STRUCTURAL PLANS.
 THE FRAMING AT THE FRONT PORCH IS DIFFERENT THAN THE
 PLANS.
  
 2) THE TRUSS DRAWINGS FOR THE MODEL E GABLE OPTION DO
 NOT HAVE THE DESIGNER OF RECORDS SHOP REVIEW STAMP ON
 THEM. THEY WILL NEED TO BE REVIEWED BY THE D.O.R. IT
 APPEARS THAT THE TRUSS LAYOUT AND DRAWINGS FOR THIS
 OPTION DOES NOT MATCH THE STRUCTURAL PLANS. THE TRUSS
 DRAWINGS HAVE A TWO PLY GIRDER (B5) NEAR THE FRONT
 PORCH AND THE STRUCTURAL DRAWING SHOW THE TRUSSES
 BEARING ON THE EXTERIOR WALL.
  
 3) THE TRUSS LAYOUT PLANS ARE NOT SIGNED AND SEALED BY
 THE TRUSS ENGINEER. FS 471 & FAC 61G-31.003
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]