2014-02-19 16:56:39 | 2010 FBC / MASTER MODEL "E" |
| |
| DENIED BY BUILDING |
| |
| 1) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS |
| THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER. |
| SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND |
| SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR |
| UNDER THE MASTER. FBC R401.3 ( NO SHEET A-0.1 WAS |
| SUBMITTED.) |
| |
| 2) REVISE WIND DESIGN DATA ON SHEET S-2 TO REFERENCE |
| THE 2010 FBC AND A WIND SPEED OF 170 MPH VULT EXPOSURE |
| C AND CHANGE ALL OTHER REFERENCES FROM THE 2007 |
| BUILDING CODE TO THE 2010 FBC. FBC R 301.2.1 |
| |
| 3) ON SHEET S-2, REVISE NOTE 2, B TO REFERENCE ACI |
| 315-08. THE 2008 EDITION IS THE ONE REFERENCED BY THE |
| 2010 FBCR OR JUST SPECIFY THE CURRENT EDITION. FBCR |
| CHAPTER 43 |
| |
| 4) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR |
| ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED |
| AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE |
| MODEL "E" STRUCTURE HIP AND GABLE ROOF OPTIONS. FBC |
| R802.1.6.1 THESE ARE REQUIRED TO BE SUBMITTED AND |
| REVIEWED FOR THE MASTER. |
| |
| 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" WIDE |
| CAST-CRETE LINTELS. THE FLORIDA COVER SHEET IS OKAY. |
| NOA NO. 12020913 FOR THE 8" WIDE LINTELS WAS NOT |
| SUBMITTED. THE ONE THAT WAS IS FOR THE 4, 6 AND 12" |
| WIDE LINTELS. DCA RULE 9N-3 |
| |
| 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE |
| MANUFACTURED SIDING (IE HARDI-BOARD) AND THE STRUCTURAL |
| CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY DCA RULE |
| 9N-3. |
| |
| 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| 8) THE PLANS LIST THE CONDITIONED SPACE AS 1096 SQFT |
| AND THE ENERGY CALCULATIONS HAVE 1072 SQFT. PLEASE |
| CLARIFY WHY THERE IS A DIFFERENCE. CITY AMENDMENTS |
| 107.2.1 |
| |
| 9) THE PLANS SHOW TWO BATHROOMS AND THE BUILDING INPUT |
| SUMMARY REPORT HAS ZERO BATHROOMS. PLEASE CALRIFY WHY |
| THERE IS A DIFFERENCE. CITY AMENDMENTS 107.2.1 |
| |
| 10) THE WINDOW SCHEDULE SPECIFIES 24 EH AND 2843 EH |
| SINGLE HUNG WINDOWS. WHAT DOES EH MEAN? THE 24 EH |
| SINGLE HUNG WINDOW IS SPECIFIED AS THE BEDROOM EGRESS |
| WINDOWS. A 24-5 SH WINDOW IS WHICH IS 37" X 56" IS |
| REQUIRED TO MEET EGRESS REQUIREMENTS. PLEASE CLARIFY. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| [email protected] |