2014-02-19 16:56:392010 FBC / MASTER MODEL "E"
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A GENERIC MODEL "E" SITE PLANS
 THAT INCLUDE SURFACE WATER DRAINAGE FOR THE MASTER.
 SITE SPECIFIC SITE PLANS WITH DRAINAGE SHOWN AND
 SURVEYS WILL BE REQUIRED FOR EACH PERMIT APPLIED FOR
 UNDER THE MASTER. FBC R401.3 ( NO SHEET A-0.1 WAS
 SUBMITTED.)
  
 2) REVISE WIND DESIGN DATA ON SHEET S-2 TO REFERENCE
 THE 2010 FBC AND A WIND SPEED OF 170 MPH VULT EXPOSURE
 C AND CHANGE ALL OTHER REFERENCES FROM THE 2007
 BUILDING CODE TO THE 2010 FBC. FBC R 301.2.1
  
 3) ON SHEET S-2, REVISE NOTE 2, B TO REFERENCE ACI
 315-08. THE 2008 EDITION IS THE ONE REFERENCED BY THE
 2010 FBCR OR JUST SPECIFY THE CURRENT EDITION. FBCR
 CHAPTER 43
  
 4) SUBMIT TWO SETS OF TRUSS DRAWINGS AND LAYOUTS FOR
 ASCE7-10, 170 MPH AND EXPOSURE C THAT HAVE BEEN SIGNED
 AND SEALED BY THE TRUSS ENGINEER AND REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR THE
 MODEL "E" STRUCTURE HIP AND GABLE ROOF OPTIONS. FBC
 R802.1.6.1 THESE ARE REQUIRED TO BE SUBMITTED AND
 REVIEWED FOR THE MASTER.
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 8" WIDE
 CAST-CRETE LINTELS. THE FLORIDA COVER SHEET IS OKAY.
 NOA NO. 12020913 FOR THE 8" WIDE LINTELS WAS NOT
 SUBMITTED. THE ONE THAT WAS IS FOR THE 4, 6 AND 12"
 WIDE LINTELS. DCA RULE 9N-3
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 MANUFACTURED SIDING (IE HARDI-BOARD) AND THE STRUCTURAL
 CONNECTORS (IE TRUSS ANCHORS) AS REQUIRED BY DCA RULE
 9N-3.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 8) THE PLANS LIST THE CONDITIONED SPACE AS 1096 SQFT
 AND THE ENERGY CALCULATIONS HAVE 1072 SQFT. PLEASE
 CLARIFY WHY THERE IS A DIFFERENCE. CITY AMENDMENTS
 107.2.1
  
 9) THE PLANS SHOW TWO BATHROOMS AND THE BUILDING INPUT
 SUMMARY REPORT HAS ZERO BATHROOMS. PLEASE CALRIFY WHY
 THERE IS A DIFFERENCE. CITY AMENDMENTS 107.2.1
  
 10) THE WINDOW SCHEDULE SPECIFIES 24 EH AND 2843 EH
 SINGLE HUNG WINDOWS. WHAT DOES EH MEAN? THE 24 EH
 SINGLE HUNG WINDOW IS SPECIFIED AS THE BEDROOM EGRESS
 WINDOWS. A 24-5 SH WINDOW IS WHICH IS 37" X 56" IS
 REQUIRED TO MEET EGRESS REQUIREMENTS. PLEASE CLARIFY.
  