2013-09-18 14:58:382008 NEC
  
 DENIED BY ELECTRIC
  
 1) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE
 MAXIMUM OVER CURRENT PROTECTION FOR THE CONDENSING UNIT
 TO BE 35 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS A 40
 AMP BREAKER. PLEASE CORRECT.
  
 2) THE MECHANICAL EQUIPMENT SCHEDULE SPECIFIES THE
 MAXIMUM OVER CURRENT PROTECTION FOR THE AIR AHANDLER
 UNIT TO BE 30 AMPS. THE ELECTRICAL PANEL SCHEDULE SHOWS
 A 45 AMP BREAKER. PLEASE CORRECT.
  
 3) PROVIDE A 2ND GROUND ROD TO MEET REQUIRED OHM
 RESISTANCE. NEC 250.56
  